401

Fanuc Alarm 401 - Servo Ready Signal Lost

VRDY Off

The servo amplifier READY signal (VRDY) was lost. The servo drive has turned off or lost enable signal.

Root Cause Summary

Fanuc 401 SERVO ALARM indicates the servo amplifier READY signal (VRDY/DRDY) for the specified axis has turned OFF, meaning the amplifier is not in operational state. This is typically caused by amplifier hardware faults, power supply issues, excessive regenerative load, DC bus voltage errors, or amplifier internal protection activation.

Safety

  • High voltage in servo cabinet
  • Lock out before inspection

Causes and Fixes

  1. 1

    Check the 7-segment LED display on the faulted axis servo amplifier module (Alpha-i or Beta-i series). Record the alarm code displayed (e.g., A.10, A.20, A.61, etc.). Refer to the amplifier manual for specific sub-alarm definitions.

  2. 2

    Navigate to DIAGNOSIS > SERVO screen and check diagnostic numbers D0300-D0307 (servo alarm history) and D0320-D0327 (amplifier status) for the affected axis to identify detailed fault conditions.

  3. 3

    Check DC bus voltage at DIAGNOSIS > SERVO, diagnostic D0020 (DC link voltage). Normal range is 280-330VDC for 200V class, 530-680VDC for 400V class. Out-of-range values indicate power supply or regenerative discharge issues.

  4. 4

    If amplifier shows overload alarm (A.10/A.20 series), inspect motor cables for shorts, check motor insulation resistance (should be >10MΩ at 500VDC test), and verify parameter 2020 (motor type code) matches the actual motor model installed.

    Disconnect motor cables before performing insulation tests to avoid damaging amplifier circuits

DIY Feasiblehigh confidence

Call a technician if:

  • ·Multiple servo amplifiers showing sub-alarms simultaneously
  • ·DC bus voltage measurements outside safe ranges
  • ·Servo control card replacement required

Prevention

  • Regular inspection of control cable connections
  • Monthly DC bus voltage monitoring
  • Keep servo amplifier cooling fans clean
  • Monitor regeneration resistor condition

Common Mistakes

  • Clearing alarm without checking amplifier sub-alarm display
  • Ignoring intermittent power supply voltage variations
  • Replacing amplifier without checking control signal wiring
  • Not documenting amplifier parameters before replacement

Related Alarms

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.