Siemens 4065 - Buffered memory was restored from backup medium (potential loss of data!)
SINUMERIK alarm 4065 occurs when the SRAM backup battery voltage drops below the minimum threshold (typically 2.7V) or when the system's internal timer indicates the battery backup duration has been exceeded. This alarm serves as an early warning before complete battery failure would cause loss of NC programs, tool offsets, and machine parameters stored in volatile SRAM.
Siemens 4065 - Buffered memory was restored from backup medium (potential loss of data!)
Buffered memory was restored from backup medium (potential loss of data!)
Control reaction: NC not ready. NC Start disable in this channel. Interface signals are set. Alarm display.
Root Cause Summary
SINUMERIK alarm 4065 occurs when the SRAM backup battery voltage drops below the minimum threshold (typically 2.7V) or when the system's internal timer indicates the battery backup duration has been exceeded. This alarm serves as an early warning before complete battery failure would cause loss of NC programs, tool offsets, and machine parameters stored in volatile SRAM.
Safety
Causes and Fixes
Check Battery Voltage in Diagnostics
Navigate to Diagnostics → Service → NCU → Hardware Info and check the SRAM battery voltage reading. Normal voltage should be 3.0-3.6V.
Document the exact voltage reading - anything below 2.8V indicates immediate replacement needed
Verify Battery Connection
Power down the system and check the battery connector on the NCU board for corrosion, loose connections, or damaged pins at X122 connector.
Always use proper ESD protection when handling NCU components
Replace SRAM Battery
Install new 3.6V lithium battery (typically BR2032 or equivalent) ensuring proper polarity. Reset battery timer via MD11210 $MN_BUFFER_TIME after replacement.
Always backup all NC data to CF card before battery replacement using Archive function
Reset Battery Monitoring
After battery replacement, reset MD11210 $MN_BUFFER_TIME to 0 and perform a warm restart to clear the alarm and restart the backup time counter.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.