Siemens SINUMERIK Controller
Servo/Axis · Intermediate · 30-120 minutes
Siemens 4071 - Check the position of the encoder
Alarm 4071 is triggered when machine data affecting absolute encoder position calculation has been modified, causing a mismatch between the encoder's absolute value and the NCK's expected machine reference position. This typically occurs after changes to MD parameters controlling encoder offset, scaling, or reference point definitions without proper re-referencing.
Siemens 4071 - Check the position of the encoder
Check the position of the encoder
Control reaction: Alarm display.
Root Cause Summary
Alarm 4071 is triggered when machine data affecting absolute encoder position calculation has been modified, causing a mismatch between the encoder's absolute value and the NCK's expected machine reference position. This typically occurs after changes to MD parameters controlling encoder offset, scaling, or reference point definitions without proper re-referencing.
Safety
Causes and Fixes
Access Siemens HMI menu: [Diagnosis] > [Axis Data] > [Encoder Information]. Verify current encoder type (absolute/incremental) and compare MD3210, MD3220, MD3230, MD3240 values against last known configuration backup or documentation.
Do not proceed with machine operation until encoder position is verified; uncontrolled axis movement may occur.
In NCK parameter editor (SINUMERIK Operate or Automation Desktop), navigate to MD3200-MD3250 for the affected axis. If parameters were recently changed, restore previous values or document the intentional modification.
Execute axis referencing procedure via [Jog] > [Reference Run] menu or issue G-code reference command (e.g., G74 for absolute encoder axes). Allow full reference cycle to complete; monitor [Actual Position] display to confirm encoder position synchronization.
Clear alarm via [Acknowledge] button (typically on HMI control panel) or issue SYS.CLEAR_ALARM(4071) in PLC program. Verify axis position readout matches machine reference after clearance.