Safety · Basic · 5 minutes to 2 hours
Siemens 3000 - Emergency stop
SINUMERIK alarm 3000 occurs when the feed override value drops to 0%, halting all axis motion. This typically results from operator panel input, hardware failure in the override potentiometer circuit, or PLC logic forcing the override to zero through interface signals.
Siemens 3000 - Emergency stop
Emergency stop
Control reaction: NC not ready. Mode group not ready, also effective for single axes. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm. Alarm reaction delay is cancelled.
Root Cause Summary
SINUMERIK alarm 3000 occurs when the feed override value drops to 0%, halting all axis motion. This typically results from operator panel input, hardware failure in the override potentiometer circuit, or PLC logic forcing the override to zero through interface signals.
Safety
Causes and Fixes
Check Physical Override Controls
Inspect the machine control panel feed override rotary switch or potentiometer. Verify it's not in the 0% position and rotate through its range to check for mechanical binding.
On older SINUMERIK systems, the override pot can develop dead spots - rotate slowly and feel for mechanical resistance.
Verify HMI Override Display
Access HMI screen 'Machine' → 'Override' and check the feed override percentage display. Use the HMI controls to increase override above 0%.
Ensure machine is in a safe state before increasing feed override as motion will resume immediately.
Test Override Response
Gradually increase feed override to 10-20% and verify the alarm clears. Test override functionality through full range (0-120%) to confirm proper operation.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.