HEIDENHAIN 238-100E - 100E UVR hardware detection faulty
This alarm specifically indicates that the control's hardware detection system cannot identify or validate the presence of the second UVR module during the boot sequence or runtime check. The root cause is typically a failure in the hardware identification circuit within the UVR module itself, damaged communication pathways on the backplane, or incompatible/corrupted module firmware that prevents proper handshake with the main control processor.
HEIDENHAIN 238-100E - 100E UVR hardware detection faulty
100E UVR hardware detection faulty
The UVR hardware detection (HIK) has detected a fault. The power supply unit cannot properly identify its hardware configuration.
Root Cause Summary
This alarm specifically indicates that the control's hardware detection system cannot identify or validate the presence of the second UVR module during the boot sequence or runtime check. The root cause is typically a failure in the hardware identification circuit within the UVR module itself, damaged communication pathways on the backplane, or incompatible/corrupted module firmware that prevents proper handshake with the main control processor.
Safety
Causes and Fixes
Power Down Control Safely
Perform a controlled shutdown of the TNC control. Switch main power OFF and wait at least 5 minutes for all capacitors to discharge before opening the control cabinet.
Always follow LOTO procedures. Verify zero voltage with multimeter before touching components.
Remove and Inspect UVR Module
Carefully extract the UVR module from slot position %2. Inspect the module label for correct type designation and part number. Check for any burn marks, damaged components, or physical damage to the PCB.
Document the original slot position and orientation. Take photos of module labels showing serial numbers and firmware versions for replacement reference.
Clean and Reseat Module
Use electronic contact cleaner on the edge connector pins of the UVR module. Clean the backplane slot contacts with compressed air and contact cleaner. Firmly reseat the module ensuring it clicks fully into position.
Apply light dielectric grease to edge connectors if operating in humid environments, but avoid over-application which can attract debris.
Test with Module Swap
If multiple UVR modules are present, swap UVR%2 with UVR%1 positions and power up. If the alarm moves to the other module position, the UVR module is defective. If alarm stays with position %2, the backplane slot is faulty.
Before swapping, enter MOD 56 (system configuration) and document current settings to verify proper detection after module exchange.
Replace Defective Module
Order exact replacement UVR module using the part number from the defective unit. Install new module and verify detection in MOD function diagnostic screen showing correct module type and firmware version.
Using incorrect UVR module types can cause system instability or damage. Always verify part number compatibility with Heidenhain technical documentation for your specific control model.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.