HEIDENHAIN 238-101D - 101D UVR configured DC-link voltage too low
The Heidenhain 238-101D alarm typically occurs when the configured DC-link voltage in MP_dcLinkVoltage is set too low compared to the rectifier value of the live line voltage. The most likely fix involves adjusting the parameter CfgSupplyModule3xx/MP_dcLinkVoltage to a value greater than the rectified line voltage, such as increasing it to DC 720 V for a 3AC 480 V line voltage.
HEIDENHAIN 238-101D - 101D UVR configured DC-link voltage too low
101D UVR configured DC-link voltage too low
The configured DC-link voltage in MP_dcLinkVoltage is too low. It must exceed the rectified value of the live line voltage.
Root Cause Summary
The Heidenhain 238-101D alarm typically occurs when the configured DC-link voltage in MP_dcLinkVoltage is set too low compared to the rectifier value of the live line voltage. The most likely fix involves adjusting the parameter CfgSupplyModule3xx/MP_dcLinkVoltage to a value greater than the rectified line voltage, such as increasing it to DC 720 V for a 3AC 480 V line voltage.
Safety
Causes and Fixes
Access Parameter Settings
Using the control panel, navigate to the machine parameters under CfgSupplyModule3xx and locate MP_dcLinkVoltage.
Ensure you have the correct access code or password to modify parameters; consult the machine manual if needed.
Ensure the machine is powered down or in a safe mode before accessing parameters to avoid electrical hazards.
Measure Line Voltage
Use a multimeter to measure the actual line voltage (e.g., 3AC 480 V) and calculate the rectified value (approximately 1.414 times the AC voltage).
Double-check multimeter settings for AC voltage to avoid incorrect readings.
High voltage present; only qualified personnel should perform this measurement.
Adjust DC-link Voltage
Set MP_dcLinkVoltage to a value greater than the rectified line voltage (e.g., DC 720 V for 3AC 480 V). Save the changes and restart the system.
Incrementally increase the value if unsure, testing after each adjustment to ensure stability.
Incorrect settings can damage components; refer to the Heidenhain manual for recommended values.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.