Heidenhain Controller
Power Supply · Intermediate · 30-120 minutes
HEIDENHAIN 238-1006 - 1006 UVR leakage current too high
The Heidenhain 238-1006 alarm, indicating high UVR leakage current, is typically caused by insulation breakdown in motor cables, power modules, or DC link connections. The most likely fix involves systematically checking and testing insulation resistance to ground using a megohmmeter and replacing or repairing damaged components. This issue often arises from environmental factors like moisture or wear over time.
HEIDENHAIN 238-1006 - 1006 UVR leakage current too high
1006 UVR leakage current too high
The UVR leakage current monitor has detected current exceeding permissible limits. There may be insulation problems in the system.
Root Cause Summary
The Heidenhain 238-1006 alarm, indicating high UVR leakage current, is typically caused by insulation breakdown in motor cables, power modules, or DC link connections. The most likely fix involves systematically checking and testing insulation resistance to ground using a megohmmeter and replacing or repairing damaged components. This issue often arises from environmental factors like moisture or wear over time.
Safety
Causes and Fixes
Disconnect Motor Cables
Power down the CNC machine and disconnect all motor cables from the power module and motor end. Ensure proper lockout/tagout procedures are followed to prevent accidental power-up.
Label each cable before disconnection to avoid mix-ups during reassembly.
Ensure the machine is fully de-energized before proceeding to avoid electrical shock.
Test Insulation Resistance
Using a megohmmeter set to 500V or 1000V (as per manufacturer specs), test the insulation resistance between each cable conductor and ground. Readings below 1 MΩ indicate insulation failure.
Perform the test in a dry environment to avoid false readings due to moisture.
Do not use a multimeter for this test; it will not provide accurate insulation resistance data.
Replace or Repair Damaged Cables
If low resistance is detected, inspect the cable for visible damage (cuts, abrasions, or burn marks). Replace the entire cable if damage is confirmed, or repair with proper insulation tape and heat-shrink tubing if minor and approved by the manufacturer.
Use only OEM-specified cables to ensure compatibility and safety.
Improper repairs can lead to recurring failures; ensure compliance with Heidenhain standards.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.