Heidenhain codes
HeidenhainPower SupplyIntermediate30-120 minutes

238-1004

HEIDENHAIN 238-1004 - 1004 UVR DC-link voltage too low

1004 UVR DC-link voltage too low

The UVR power supply unit reports DC-link voltage below acceptable levels. The power system cannot maintain proper voltage.

Root Cause Summary

HEIDENHAIN alarm 238-1004 indicates the UVR (Undervoltage Release) monitoring has detected DC-link voltage below the minimum threshold in the power supply unit. This typically occurs due to input power issues, power supply component failure, or excessive load conditions affecting the DC bus voltage regulation.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Check input voltage at main disconnect

    Measure incoming 3-phase voltage at the main power disconnect. Verify voltage is within ±10% of rated voltage (typically 400V/480V) and all phases are balanced.

    Use proper PPE and lockout procedures when working with high voltage

  2. 2

    Monitor voltage during operation

    Use oscilloscope or power quality analyzer to check for voltage sags, spikes, or dropouts during machine operation cycles that could cause momentary DC-link undervoltage.

    Check voltage during high-load operations like rapid traverse or spindle acceleration

  3. 3

    Verify power supply input connections

    Inspect all input power connections to the TNC power supply module for loose connections, corrosion, or overheating signs at terminal blocks.

    Use thermal imaging to identify hot connections under load

  4. 4

    Check building power quality

    Coordinate with facility maintenance to verify building power quality, transformer loading, and any recent electrical work that might affect voltage stability.

Service Recommendedmedium confidence

Call a technician if:

  • ·High voltage measurements required
  • ·Power supply module replacement needed
  • ·Rectifier bridge testing required
  • ·UVR circuit calibration needed

Prevention

  • Install power line conditioning equipment
  • Perform annual capacitor ESR testing
  • Monitor building power quality regularly
  • Keep power supply ventilation clear

Common Mistakes

  • Not allowing proper DC-link discharge time
  • Replacing individual capacitors instead of complete bank
  • Ignoring building power quality issues
  • Adjusting UVR thresholds without proper calibration