HEIDENHAIN 126-011D - Self-test was not executed on with HSCI address
The HSCI component at the specified address has either failed to execute its mandatory self-test during initialization or failed to communicate the self-test completion back to the TNC control. This is a safety interlock preventing machine operation until all components have verified their operational readiness through successful self-test completion.
HEIDENHAIN 126-011D - Self-test was not executed on with HSCI address
Self-test was not executed on with HSCI address
This TNC7/TNC 640 error (126-011D) relates to 'Self-test was not executed on with HSCI address '. During the device self-test, an expected message was not received.
Root Cause Summary
The HSCI component at the specified address has either failed to execute its mandatory self-test during initialization or failed to communicate the self-test completion back to the TNC control. This is a safety interlock preventing machine operation until all components have verified their operational readiness through successful self-test completion.
Safety
Causes and Fixes
Perform clean system restart
Ensure Emergency Stop is released. Power down the complete system using the main disconnect. Wait minimum 30 seconds for all capacitors to discharge. Power up and allow the TNC to complete its full boot sequence without any interruption—do not press any keys or activate E-Stop during HSCI initialization phase (typically 30-90 seconds).
Do not interrupt the boot sequence once started. Wait for the TNC to reach the normal operating screen or error state.
Monitor HSCI initialization
During boot-up, observe the TNC screen for HSCI initialization messages. The control will display status of each HSCI component as it completes self-test. Note if the component at address %3 is listed and whether it completes or times out.
Press MOD key → Info → Boot Log to review the complete startup sequence and identify at which point the component failed to respond.
Verify alarm clearance
After successful uninterrupted boot, check if alarm 126-011D clears automatically. If cleared, perform a test cycle of all axes to verify normal operation. Document the incident and monitor for recurrence.
If this alarm occurs repeatedly at startup, suspect hardware issues rather than initialization timing problems.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?