HEIDENHAIN 126-012F - Component: with serial number: not planned in project
The control's hardware configuration project does not include the serial number of a component that is physically present and communicating on the system bus. This mismatch between planned configuration and detected hardware prevents proper initialization. The issue is resolved by updating the hardware configuration file to match the actual installed components.
HEIDENHAIN 126-012F - Component: with serial number: not planned in project
Component: with serial number: not planned in project
A Gen 3 system requires every HSCI-connected component and all power modules to be present in the IOconfig project. The indicated component is missing from that plan.
Root Cause Summary
The control's hardware configuration project does not include the serial number of a component that is physically present and communicating on the system bus. This mismatch between planned configuration and detected hardware prevents proper initialization. The issue is resolved by updating the hardware configuration file to match the actual installed components.
Safety
Causes and Fixes
Identify the unplanned component
Record the component name (%1) and serial number (%2) from the alarm display. Common components include PLCxxxx (PLC module), CCxxxx (CC control unit), UMxxxx (drive modules), or IBxxxx (encoder interfaces).
Launch TNCopt commissioning software
Connect to the control using TNCopt (version must match control software version). Navigate to the hardware configuration section and perform a bus scan to detect all physically present components.
Update hardware configuration
In TNCopt, compare the scanned hardware against the project configuration. Accept the new serial number by either replacing the old component entry or adding the component if missing. Ensure all parameters and assignments are correctly transferred.
Before accepting changes, document the old serial number and save a backup of the current configuration file in case the new component needs to be reverted.
Save and transfer updated configuration
Save the modified hardware project in TNCopt and transfer the updated TNCopt.sys file to the control's SYS directory, overwriting the existing configuration file.
Perform cold start
Execute a complete system restart (power cycle or MOD → Reset → Cold Start) to force the control to reload the hardware configuration and reinitialize all components with the updated project.
Cold start will reset PLC program execution and clear certain system states. Coordinate with production before executing.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?