Fanuc Alarm 605 - n AXIS: CNV. EX. DISCHARGE POWER
Fanuc Alarm 605 CNV. EX. DISCHARGE POWER occurs when the PSM (Power Supply Module) or αi-PS regenerative discharge circuit is overloaded due to excessive regenerative energy returning from servo motors during deceleration. The internal discharge resistor cannot dissipate the energy fast enough, causing the DC bus voltage to rise beyond safe limits and triggering the protective alarm.
Fanuc Alarm 605 - n AXIS: CNV. EX. DISCHARGE POWER
FANUC ALARM 605
PSMR: Regenerative power is too large. Reduce deceleration rates or add external regenerative resistor.
Root Cause Summary
Fanuc Alarm 605 CNV. EX. DISCHARGE POWER occurs when the PSM (Power Supply Module) or αi-PS regenerative discharge circuit is overloaded due to excessive regenerative energy returning from servo motors during deceleration. The internal discharge resistor cannot dissipate the energy fast enough, causing the DC bus voltage to rise beyond safe limits and triggering the protective alarm.
Causes and Fixes
Monitor DC bus voltage during alarm occurrence via DIAGNOSIS > SERVO > DC LINK VOLTAGE screen (specific diagnosis number varies by series: #300-#399 range). Normal voltage is 280-310VDC for 200V class, alarm typically triggers above 380-400VDC.
Check servo parameters 1620 (time constant for acceleration) and 1621 (time constant for deceleration) for all axes. Increase Parameter 1621 values by 20-30% to slow deceleration rate and reduce regenerative peak power.
Review rapid traverse override settings and program G00 moves. Reduce rapid feedrate (Parameter 1420) or feedrate override if deceleration distances are insufficient for the load inertia.
If alarm persists after deceleration adjustments, calculate total regenerative power requirements and install external regenerative resistor unit matched to PSM capacity. Consult amplifier specifications for maximum continuous and peak regenerative power ratings.
External resistor installation requires proper wiring to PSM terminals RB1/RB2 and setting Parameter 8905#0 (regenerative resistor selection bit) correctly per Connection Manual
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.