Fanuc Alarm 607 - n AXIS: CNV. SINGLE PHASE FAILURE

FANUC ALARM 607

PSM or PSMR: Input voltage is in open-phase condition. Check incoming AC power supply and all three phases.

Root Cause Summary

Alarm 607 indicates the Power Supply Module (PSM) or Power Supply Module Regenerative (PSMR) has detected a missing or failed phase on the incoming three-phase AC power supply. This typically occurs when one of the three incoming AC phases (R, S, T or L1, L2, L3) is open, has low voltage, or experiences severe imbalance exceeding the converter's tolerance threshold.

Causes and Fixes

  1. 1

    Power down the system completely. Use a multimeter to measure incoming AC voltage at the primary power disconnect or main breaker feeding the CNC. Verify all three phases (R-S, S-T, T-R) show balanced voltage within 2-3% of nominal (200VAC, 220VAC, 400VAC, 480VAC depending on system).

    HIGH VOLTAGE - Use proper PPE and lockout/tagout procedures. Only qualified electricians should perform this measurement.

  2. 2

    Check all fuses, circuit breakers, and contactors in the main power circuit feeding the CNC cabinet. Inspect fuse holders for corrosion or loose connections. Replace any blown fuses or defective circuit protection devices.

    Ensure replacement fuses match the OEM-specified ratings found on the electrical schematic.

  3. 3

    Inspect terminal blocks TB1 or TB2 (depending on system) at the PSM/PSMR module for loose, burned, or corroded connections on the L1, L2, L3 input terminals. Torque all connections to specification (typically 1.2-1.5 N-m for PSM terminals).

  4. 4

    Navigate to SYSTEM > DIAGNOSIS > PSM (screen number varies by series: typically #0300 for 0i/30i/31i/32i). Check diagnostic registers DC voltage output and AC input voltage readings. Compare all three phases for balance and proper voltage levels.

DIY Feasiblehigh confidence

Call a technician if:

  • ·PSM module replacement required
  • ·Facility electrical system modifications needed
  • ·Power quality issues beyond machine scope

Prevention

  • Install power quality monitoring
  • Perform regular electrical connection inspections
  • Maintain proper facility power system
  • Use surge protection devices

Common Mistakes

  • Not checking all three phases individually
  • Ignoring voltage imbalance issues
  • Replacing PSM without verifying input power quality
  • Not following proper LOTO procedures during electrical checks

Related Alarms

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.