Siemens SINUMERIK Controller
Servo/Axis · Intermediate · 30-120 minutes
Siemens 300888 - Axis drive parameterization error in current control adaption
This alarm occurs when the upper current limit in MD 1181 is set lower than the lower current limit in MD 1180, causing a parameterization error in current control adaption. Correct the values in the machine data to resolve it.
Siemens 300888 - Axis drive parameterization error in current control adaption
Axis drive parameterization error in current control adaption
The upper current limit in MD 1181: $MD_CURRCTRL_ADAPT_CURRENT_2 (upper adaption current limit) is less than the lower current limit in MD 1180: $MD_CURRCTRL_ADAPT_CURRENT_1 (lower adaption current limit) Control reaction: Interface signals are set. Alarm display.
Root Cause Summary
This alarm occurs when the upper current limit in MD 1181 is set lower than the lower current limit in MD 1180, causing a parameterization error in current control adaption. Correct the values in the machine data to resolve it.
Safety
Causes and Fixes
Access machine data
Navigate to the machine data settings in the Siemens control panel.
Verify and correct values
Ensure MD 1181 ($MD_CURRCTRL_ADAPT_CURRENT_2) is greater than MD 1180 ($MD_CURRCTRL_ADAPT_CURRENT_1). Adjust as needed.
Save and restart
Save the changes, clear the alarm, and restart the system to apply the new settings.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.