HEIDENHAIN 230-01B0 - Error in spindle positioning
This alarm occurs when the spindle cannot complete an M19 oriented stop within the configured monitoring window. The root cause is typically either improper machine parameter configuration (especially timeout and tolerance values), mechanical issues preventing precise positioning, or feedback system problems with the spindle encoder that prevent the control from accurately measuring spindle position.
HEIDENHAIN 230-01B0 - Error in spindle positioning
Error in spindle positioning
A spindle-positioning move did not finish correctly. The most common cause is that the M19 maximum speed parameter is set too low.
Root Cause Summary
This alarm occurs when the spindle cannot complete an M19 oriented stop within the configured monitoring window. The root cause is typically either improper machine parameter configuration (especially timeout and tolerance values), mechanical issues preventing precise positioning, or feedback system problems with the spindle encoder that prevent the control from accurately measuring spindle position.
Safety
Causes and Fixes
Access spindle monitoring parameters
Navigate to MOD function (press MOD key) → Machine Parameters → enter filter '1260' to locate MP1260 SPIND. POSITIONING TIME
Typical values range from 2-10 seconds depending on spindle mass and drive performance
Check current timeout value
Review MP1260 current setting. If less than 3 seconds on larger spindles or less than 1 second on smaller spindles, value is likely insufficient
Note the current value before making changes - document original machine parameters
Perform test orientation
In MDI mode, execute M19 command and use stopwatch to measure actual positioning time. MP1260 should be set to 150-200% of measured time
Add 1-2 seconds buffer to account for variations in load and starting position
Adjust MP1260 if necessary
Increase MP1260 value incrementally (add 2-3 seconds). Power cycle control or execute 'Reset All' from positioning menu to activate new parameter
Parameter changes require machine manufacturer authorization - verify warranty implications
Call a technician if:
Prevention