HEIDENHAIN 230-001A - A parameter change requires the drive to be switched off (axis)
The TNC control has detected a parameter modification in the drive configuration that cannot be applied while the drive inverter is powered and operational. This is a protective mechanism to ensure drive parameters are properly initialized during the power-up sequence, preventing potential drive faults or motor damage from incompatible runtime parameter changes.
HEIDENHAIN 230-001A - A parameter change requires the drive to be switched off (axis)
A parameter change requires the drive to be switched off (axis)
During reconfiguration or parameter-set switching, a parameter was altered that demands the drive to be off beforehand. The change was not accepted.
Root Cause Summary
The TNC control has detected a parameter modification in the drive configuration that cannot be applied while the drive inverter is powered and operational. This is a protective mechanism to ensure drive parameters are properly initialized during the power-up sequence, preventing potential drive faults or motor damage from incompatible runtime parameter changes.
Safety
Causes and Fixes
Identify Changed Motor Parameters
Navigate to MOD > System Parameters > Axes > [Affected Axis] > Motor. Review parameters such as motorType, motorRatedCurrent, motorPolePairs, or motorTable entries. Compare against previous backup or documentation.
Press HELP key while cursor is on parameter to see detailed description and valid value ranges specific to your TNC version.
Verify Parameter Compatibility
Cross-reference the changed parameter values with the actual motor nameplate data. Ensure motor type codes match the installed motor (synchronous vs. asynchronous, frameless, etc.).
Incorrect motor parameters can cause thermal overload, reduced torque, or motor damage. Always verify against motor documentation.
Execute Controlled Power Cycle
Enter PLC STOP mode, engage Emergency Stop, turn OFF main cabinet power. Wait minimum 10 seconds for capacitor discharge. Power ON and allow complete boot sequence. The drive will initialize with new parameters.
Ensure no workpiece collision risk exists before referencing axes after parameter changes.
Perform Test Reference
After power-up, manually reference the affected axis in MDI mode. Monitor for smooth motion, proper reference point acquisition, and absence of current alarms or motor cogging.
Use MOD > Diagnosis > Axes > [Axis] > Position Monitor to observe actual vs. commanded position during initial moves.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.