HEIDENHAIN 1A0-0194 - The limit switches of a modulo axis are invalid
The fundamental issue is a configuration conflict where an axis is simultaneously defined as modulo (unlimited continuous rotation via MP1010) and restricted by limit switches (hardware inputs or software limits in MP1020/MP1030). Heidenhain TNC controls enforce logical consistency by generating this alarm when detecting this incompatible configuration, as modulo axes by definition have no travel limits.
HEIDENHAIN 1A0-0194 - The limit switches of a modulo axis are invalid
The limit switches of a modulo axis are invalid
The software limits or protection zones set for a modulo axis violate one or more geometric rules. Valid limits must stay within a single 360-degree window with the lower bound above -360° and the upper bound below +360°, and the two must not overlap or leave gaps.
Root Cause Summary
The fundamental issue is a configuration conflict where an axis is simultaneously defined as modulo (unlimited continuous rotation via MP1010) and restricted by limit switches (hardware inputs or software limits in MP1020/MP1030). Heidenhain TNC controls enforce logical consistency by generating this alarm when detecting this incompatible configuration, as modulo axes by definition have no travel limits.
Safety
Causes and Fixes
Access machine parameters in service mode
Enter MOD function, select 'Machine Parameters', and authenticate with appropriate password level (typically OEM or service level required for MP access)
Document all existing parameter values before making changes. Incorrect machine parameters can cause machine damage or unexpected behavior.
Identify the affected modulo axis
Review the alarm context or check MP1010 for all axes. The affected axis will have MP1010.x set to a non-zero value (e.g., 360 for degrees, 400 for gon). Note the axis number/letter (x = axis index).
Check and clear software limit parameters
For the identified axis, check MP1020.x (positive software limit) and MP1030.x (negative software limit). For modulo axes, these MUST be set to inactive values. Set MP1020.x = 9999999999 and MP1030.x = -9999999999 (or per machine manufacturer specification).
Some machine manufacturers use different inactive values. Check MP documentation or compare with other known-good modulo axes on the same machine model.
Save parameters and restart control
Save the modified machine parameters, exit the parameter editor, and perform a full control restart (power cycle or controlled restart via MOD functions) to ensure parameters take effect.
Ensure all machine motion is stopped and safe before restarting the control.
Verify axis configuration
After restart, navigate to Test -> Axis diagnostic and verify the affected axis shows as 'Modulo' type with no limit switch indicators active. Test axis motion across the modulo boundary (e.g., move from 350° to 10°).
Use MDI mode to execute a controlled test move that crosses the modulo rollover point to confirm proper continuous rotation without limit interference.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.