HEIDENHAIN 126-0118 - PLC output for switch-off is improperly configured
This alarm specifically indicates that a PLC output designated for safety-critical switch-off functionality has not been properly declared in the control's configuration. The TNC requires explicit configuration of outputs used for emergency stop, power disconnect, or other safety shutdown functions through machine parameters or the SIK.SYS file. The PLC program references an output for switch-off purposes, but the system configuration does not recognize it as a valid, configured output.
HEIDENHAIN 126-0118 - PLC output for switch-off is improperly configured
PLC output for switch-off is improperly configured
Automatic machine power-down after control shutdown is enabled, yet no PLC output was configured for this task in either the configuration file or the IOC file. The function therefore has no actuator to drive.
Root Cause Summary
This alarm specifically indicates that a PLC output designated for safety-critical switch-off functionality has not been properly declared in the control's configuration. The TNC requires explicit configuration of outputs used for emergency stop, power disconnect, or other safety shutdown functions through machine parameters or the SIK.SYS file. The PLC program references an output for switch-off purposes, but the system configuration does not recognize it as a valid, configured output.
Safety
Causes and Fixes
Enter MOD function
Press MOD key, enter password if required, and navigate to machine parameters section
Changing machine parameters may affect machine safety functions. Document original values before making changes.
Check MP7200
Locate MP7200 (Number of digital outputs) and verify the value matches or exceeds the highest output number used in your PLC program for switch-off functions
Configure MP7210.x
Find the specific MP7210.x entry corresponding to the output number used for switch-off (x = output number). Configure the output with proper assignment to the physical hardware address and output type
MP7210 uses format: output number, hardware address, output type (0=standard, 1=safety). For safety switch-off functions, ensure proper type is set.
Cycle power
After saving parameters, perform a complete power cycle of the control (not just RESET) to ensure new output configuration is loaded into the PLC runtime
Call a technician if:
Prevention
Common Mistakes
Related Alarms