axismd.ai
Haas Controller
System · Intermediate · 15 - 45 min
Haas Alarm 1240 - Mist Collector Fault
Alarm 1240 occurs when the Haas NGC control fails to receive proper feedback confirmation from the mist collector system within the programmed timeout period. The control sends an enable signal to start the mist collector and expects a run-confirm feedback signal, but when this feedback is absent or delayed, the alarm triggers and typically locks out spindle operation for safety.
Haas Alarm 1240 - Mist Collector Fault
Mist Collector Fault
This alarm indicates the mist collector system has failed to operate properly or the control has lost feedback from the mist collector unit. The MOCON board monitors the mist collector relay output and expects feedback confirming operation. The machine will not run automatic cycles until this is cleared because coolant mist extraction is considered a safety requirement.
Root Cause Summary
Alarm 1240 occurs when the Haas NGC control fails to receive proper feedback confirmation from the mist collector system within the programmed timeout period. The control sends an enable signal to start the mist collector and expects a run-confirm feedback signal, but when this feedback is absent or delayed, the alarm triggers and typically locks out spindle operation for safety.
Safety
Causes and Fixes
Check Mist Collector Power and Operation
Verify the mist collector unit is receiving power and attempting to start when commanded. Listen for motor startup sounds and check unit status lights.
Ensure main power is locked out before checking electrical connections
Inspect Feedback Wiring
Check the run-confirm feedback wire from the mist collector to the machine control cabinet. This is typically a 24VDC signal wire that should show continuity and proper voltage when collector is running.
Use a multimeter to verify 24VDC present on feedback wire when collector motor is running
Test Feedback Relay in Collector
Most mist collectors use an internal relay to provide run confirmation. Check if this relay is functioning by measuring continuity across its contacts when unit is running.
Relay contacts may be worn or stuck - try manually cycling the collector on/off several times
Verify Control Input Signal
At the machine control cabinet, verify the feedback signal is reaching the input card. Check input LED status and measure voltage at the input terminal.
Input should show 24VDC when collector is running, 0VDC when stopped
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.