FANUC codes
FANUCSpindleIntermediate5-30 minutes

566

Fanuc 566 - Spindle temperature sensor error

SPINDLE TEMPERATURE SENSOR ERROR

Fanuc spindle alarm 566: SPINDLE TEMPERATURE SENSOR ERROR. The spindle drive or spindle motor has detected a fault condition that requires diagnosis before spindle operation can resume.

Root Cause Summary

Alarm 566 indicates the spindle amplifier is not receiving a valid temperature signal from the thermistor embedded in the spindle motor windings. This can result from a faulty thermistor, damaged sensor wiring between motor and drive, or a failed temperature monitoring circuit in the spindle amplifier itself.

Safety

  • Verify corrected program or parameters before resuming machining

Causes and Fixes

  1. 1

    Power off the machine and LOTO. Check the spindle motor terminal box for loose, corroded, or damaged thermistor connections (typically labeled TH1/TH2 or similar).

    Verify zero voltage before touching any connections.

  2. 2

    At the spindle amplifier, inspect the temperature sensor connector (consult amplifier manual for specific terminals). Look for bent pins, corrosion, or loose connections.

  3. 3

    Measure thermistor resistance at the motor terminal block with an ohmmeter. A healthy PT100 or PTC thermistor should read approximately 100-150 ohms at room temperature. Open circuit (infinite) or short (zero) indicates failure.

  4. 4

    If resistance is normal at motor but alarm persists, check continuity through the entire cable run from motor to amplifier to isolate cable damage.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.