Siemens SINUMERIK codes
Siemens SINUMERIKSafetyIntermediate30-120 minutes

27222

Siemens 27222 - PROFIsafe: S7 F module PROFIsafe address unknown

PROFIsafe: S7 F module PROFIsafe address unknown

The F module with the specified PROFIsafe address has not been parameterized as an F module in the NCK MD Control reaction: Mode group not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.

Root Cause Summary

Alarm 27222 indicates that a PROFIsafe F module with the specified address has been detected on the PROFINET network but has not been properly configured as an F module in the NCK Machine Data. The NCK safety kernel cannot establish communication with an unparameterized F module, preventing PROFIsafe function block execution and safety-critical operations.

Safety

  • Only qualified personnel should diagnose and clear control alarms; follow the machine builder's safety procedures and lockout/tagout where hardware work is required.

Causes and Fixes

  1. 1

    Access Siemens SINUMERIK 840D HMI or SCOUT TIA. Navigate to Diagnosis > Alarms and note the exact PROFIsafe address %1 value from alarm 27222.

  2. 2

    Open NCK Machine Data editor. Navigate to MD 37100 (PROFIsafe module configuration) and verify that an F module declaration exists with the address matching the alarm. Check MD 37101 through MD 37120 range for F module type and IO mapping assignments.

    Editing MD parameters requires service level access; backup current configuration before modifications.

  3. 3

    If the F module address is missing, add a new F module entry with the correct PROFIsafe address. Assign appropriate F module type (e.g., F-DI, F-DO, F-AI) matching the actual hardware module type connected to PROFINET.

  4. 4

    Perform a complete NCK initialization or warm start (startup mode 2 or 3) to reload Machine Data. Verify alarm clears and F module PROFIsafe communication is established in Diagnostics > PROFIsafe Status.

    Warm start will interrupt program execution; coordinate with production scheduling.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.