axismd.ai
Siemens SINUMERIK Controller
Safety · Intermediate · 30-120 minutes
Siemens 27221 - PROFIsafe: NCK F module MD [ ] unknown
Alarm 27221 indicates a mismatch between the F module configured in machine data (MD) and the corresponding PROFIsafe address defined in the S7 PROFIBUS configuration. The NCK cannot resolve the F module identity at the specified PROFIsafe slave address, preventing safe communication initialization.
Siemens 27221 - PROFIsafe: NCK F module MD [ ] unknown
PROFIsafe: NCK F module MD
The F module parameterized in the specified machine data is unknown under this PROFIsafe address in the S7 PROFIBUS configuration Control reaction: Mode group not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.
Root Cause Summary
Alarm 27221 indicates a mismatch between the F module configured in machine data (MD) and the corresponding PROFIsafe address defined in the S7 PROFIBUS configuration. The NCK cannot resolve the F module identity at the specified PROFIsafe slave address, preventing safe communication initialization.
Safety
Causes and Fixes
Access HMI Diagnostics > Machine Data menu and verify MD 30200 (F_MODULE_TYPE) and MD 30201 (F_MODULE_ADDRESS). Document the module type and PROFIBUS address specified.
Open the S7-PLCSIM or STEP 7 project in TIA Portal. Navigate to PROFIBUS master configuration and locate the slave device at the address from MD 30201. Verify the F module type matches MD 30200.
If using legacy SIMATIC S7-300, open STEP 7 Classic and check the PROFIBUS configuration under CPU > DP/Master > Slaves.
Compare the module identification (e.g., 6ES7 partner number) in the S7 configuration against the physical F module installed or the expected module type per machine data. If mismatch found, either update MD 30200/30201 or reconfigure the S7 PROFIBUS slave entry.
After correcting the configuration, perform a cold start (power-down/power-up) to force NCK reload of machine data and PROFIsafe parameter validation.
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.