Siemens SINUMERIK codes
Siemens SINUMERIKServo/AxisIntermediate30-120 minutes

26020

Siemens 26020 - Axis encoder hardware fault during encoder initialization

Axis encoder hardware fault during encoder initialization

Error during initialization of encoder (refer to additional information for absolute encoder interface from error fine coding). The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready) Control reaction: Mode group not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Axes of this channel must be re-referenced. Interface signals are set. Alarm display. NC Stop on alarm. Channel not ready.

Root Cause Summary

Alarm 26020 occurs when the NCK fails to initialize the encoder interface during axis startup, typically due to hardware communication failures, misconfigured encoder parameters (MD20080-MD20089 range), or defective transducer feedback devices. This prevents the axis from reaching READY status and blocks channel operation until the encoder handshake completes successfully.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Causes and Fixes

  1. 1

    Power cycle the machine and observe if alarm 26020 repeats on the same axis. Use Diagnostics → Alarms → Active to confirm encoder %2 identifier and fault code %3 in the NCK.

    Do not jog or rapid the axis while this alarm is active

  2. 2

    Physically inspect the encoder connector (M23 or M12 depending on type) at both the transducer and control card for corrosion, bent pins, or loose seating. Check cable continuity with a multimeter on the signal lines referenced in the axis configuration (typically Encoder.Connector in Automation Studio hardware tree).

  3. 3

    In NCK → Diagnostics → Encoders, verify the encoder type matches the hardware (MD20080 ENCODER_TYPE for the axis). Compare against the actual encoder nameplate (e.g., SSI, EnDat 2.2, DRIVE-CLiQ). If mismatch exists, correct MD20080 and perform a warm restart via Diagnostics → System Info → Restart NCK.

    Incorrect encoder type will always trigger 26020 during initialization

  4. 4

    If hardware appears sound, swap the encoder cable with a known-good axis cable of identical type. If alarm migrates to the other axis, the original cable is faulty. If alarm remains on the original axis, the encoder or control card input is defective and requires component replacement.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.