Siemens SINUMERIK codes
Siemens SINUMERIKServo/AxisIntermediate30-120 minutes

26019

Siemens 26019 - Axis encoder measurement not possible with this controller module

Axis encoder measurement not possible with this controller module

If the MD MD13100 $MN_DRIVE_DIAGNOSIS[8] contains a value not equal to zero, then the control has found at least one control module which does not support measuring. Measuring was programmed from the part program for the associated axis Control reaction: Local alarm reaction. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.

Root Cause Summary

Alarm 26019 is triggered when a MEASURE command is executed in the part program (G65 or similar measuring cycle) but the control module assigned to the specified axis does not support the measuring function. The MD $MN_DRIVE_DIAGNOSIS[8] diagnostic parameter detects incompatible drive hardware or firmware that lacks measurement capability.

Safety

  • Drive/power/encoder circuit: hazardous voltages may remain in the DC link after power-off. Lock out / tag out, wait for discharge per the drive documentation, and use qualified personnel only.

Causes and Fixes

  1. 1

    Check the drive type assignment in NCK menu: Diagnosis > Drive > Axis Configuration. Verify that the axis uses a measurement-capable drive module listed in the system documentation (e.g., SIMODRIVE 611 with measuring input, not basic stepper modules).

    Do not attempt to enable measuring on unsupported drive hardware.

  2. 2

    Inspect MD $MN_DRIVE_DIAGNOSIS[8] value via HMI Diagnostics menu or Service menu. A non-zero value indicates which drive module lacks measurement support. Document the axis number and drive module identification.

  3. 3

    Verify encoder cable connection to the drive's measurement input terminals. Confirm encoder type matches drive expectations (absolute/incremental). Check MD $MN_ENCODER_TYPE[axis] parameter aligns with physical encoder hardware.

    Loose or reversed encoder connectors will prevent measurement capability detection.

  4. 4

    If hardware is correct, update drive firmware via SIEMENS Service Tool. Measuring functionality may require minimum firmware revision level on the servo module.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.