Siemens 26009 - Axis QEC: memory overflow

Axis QEC: memory overflow

The product of the data $AA_QEC_COARSE_STEPS+1 and $AA_QEC_FINE_STEPS must not exceed the maximum number of the characteristic curve points (MD38010 $MA_MM_QEC_MAX_POINTS). With a direction- dependent characteristic, this criterion applies to 2 * ($AA_QEC_COARSE_STEPS+1) * $AA_QEC_FINE_STEPS! Control reaction: Alarm display.

Root Cause Summary

Alarm 26009 fires when the QuickErrorCompensation (QEC) memory buffer overflows due to excessive characteristic curve points exceeding MD $MA_MM_QEC_MAX_POINTS. This occurs when the product of coarse and fine interpolation steps, optionally doubled for direction-dependent characteristics, exceeds the NCK allocated memory for QEC lookup tables.

Safety

  • Only qualified personnel should diagnose and clear control alarms; follow the machine builder's safety procedures and lockout/tagout where hardware work is required.

Causes and Fixes

  1. 1

    Navigate to Diagnostics > Parameters > Machine Data (MD) on the SINUMERIK 840D HMI. Query MD $MA_MM_QEC_MAX_POINTS to determine the maximum allowed characteristic points for your system (typically 16384 or 32768 depending on NCK memory configuration).

  2. 2

    Check axis-specific MD $AA_QEC_COARSE_STEPS and $AA_QEC_FINE_STEPS values. Calculate: ($AA_QEC_COARSE_STEPS+1) × $AA_QEC_FINE_STEPS. If MD $AA_QEC_DIRECTION_DEPENDENT is set to 1, double this product. Compare against $MA_MM_QEC_MAX_POINTS.

    If direction-dependent QEC is active, memory requirement doubles—verify via MD $AA_QEC_DIRECTION_DEPENDENT = 0 or 1.

  3. 3

    Reduce either $AA_QEC_COARSE_STEPS or $AA_QEC_FINE_STEPS to lower the total characteristic point count. For example, decrease $AA_QEC_FINE_STEPS from 16 to 8, recalculating the product to remain below $MA_MM_QEC_MAX_POINTS.

  4. 4

    If direction-dependent compensation is not essential, set MD $AA_QEC_DIRECTION_DEPENDENT = 0 to halve memory consumption. Recompile and transfer the QEC characteristic curve data ($AA_QEC_POLY_COEFF array) to the NCK, then reset the axis alarm.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.