axismd.ai
Heidenhain Controller
Servo/Axis · Intermediate · 30-120 minutes
Heidenhain 260-020E - Compilation of PLC error table failed
The PLC compiler has encountered errors while attempting to compile the error table definitions, preventing the control from properly establishing PLC-based error handling. This is typically caused by syntax errors, file corruption, or format incompatibility in the PLCE.TAB file. The control cannot continue with PLC operations until the error table compiles successfully.
Heidenhain 260-020E - Compilation of PLC error table failed
Compilation of PLC error table failed
This alarm occurs when the Heidenhain control's PLC compiler cannot successfully compile the PLC error table (PLCE.TAB or error handling structures) during system startup or after PLC program modifications. The PLC error table defines custom error messages and handling routines for machine-specific conditions. Compilation failure prevents proper PLC error message display and handling.
Root Cause Summary
The PLC compiler has encountered errors while attempting to compile the error table definitions, preventing the control from properly establishing PLC-based error handling. This is typically caused by syntax errors, file corruption, or format incompatibility in the PLCE.TAB file. The control cannot continue with PLC operations until the error table compiles successfully.
Safety
Causes and Fixes
Access PLC programming environment
Press MOD key, select 'PLC Programming' or access via Settings → General → MOD functions → PLC. Enter service password if required for your control generation.
On iTNC 530 and TNC 620/640, you can access PLC files directly through the File Manager in PLC operating mode.
Review compilation error log
Check the PLC compiler output window or error log for specific error messages indicating line numbers, syntax issues, or invalid error number ranges. Note any E-number conflicts or format violations.
Heidenhain PLC error numbers must be in the range E1000-E9999 for user-defined errors.
Open and inspect PLCE.TAB
Navigate to TNC:\plc\ directory and open PLCE.TAB file. Verify proper format: error number, language identifier, error text in quotes, proper delimiters. Check for special characters, missing quotes, or incorrect line termination.
Each error definition must follow format: E#### "Error text in English" or E#### DE "Fehlertext" for German. No semicolon needed at line end.
Validate error number ranges
Ensure all error numbers are within valid ranges and not duplicated. User PLC errors must use E1000-E9999 range. Remove any conflicting or out-of-range definitions.
Do not use error numbers E0001-E0999 as these are reserved for Heidenhain system errors.
Recompile and test
Save corrections to PLCE.TAB, then manually trigger PLC compilation via 'Compile All' in PLC programming mode. Verify compilation completes without errors before exiting.
Always keep a backup of working PLCE.TAB file on external media before making changes.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.