HEIDENHAIN 231-E031 - E031 CC FS outputs not "0" 0-31: 32-63

E031 CC FS outputs not "0" 0-31: 32-63

During the watchdog test of the safety self-test, FS outputs 0-63 remained set although they should have been reset. A short circuit of an FS output to +24 V or defective hardware can cause this.

Root Cause Summary

HEIDENHAIN alarm 231-E031 occurs when the safety system's watchdog test detects that Fail-Safe (FS) outputs remain active when they should be reset to '0' state. This indicates either a hardware short circuit to +24V on the FS output channels or a defective safety module component.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Decode FS Output Status

    Convert the bit-encoded values %4 (outputs 0-31) and %5 (outputs 32-63) from decimal to binary to identify which specific FS outputs are stuck high.

    Use Windows calculator in programmer mode or create a binary conversion chart for quick field diagnosis

  2. 2

    Isolate Affected FS Outputs

    Disconnect the external wiring from the identified FS output terminals on the CC unit. Check if alarm clears after power cycle.

    Ensure machine is in safe state and follow LOTO procedures before disconnecting safety circuits

  3. 3

    Test External Wiring

    Measure resistance between the disconnected FS output wires and +24V supply using a multimeter. Resistance should be >1MΩ.

    Check for moisture ingress in junction boxes and damaged cable insulation in cable chains

  4. 4

    Verify FS Output Module

    If external wiring tests good, the FS output module on the CC unit may be defective and requires replacement.

    FS output module replacement requires safety system re-commissioning and validation

Service Recommendedhigh confidence

Call a technician if:

  • ·Safety system alarms require certified technician
  • ·FS output hardware replacement needed
  • ·Safety configuration corruption detected
  • ·CC unit replacement required

Prevention

  • Regular safety system validation testing
  • Maintain proper cable shielding and routing
  • Monitor power supply quality
  • Keep safety configuration backups current

Common Mistakes

  • Attempting to force-clear safety alarms
  • Bypassing safety circuits for troubleshooting
  • Modifying safety parameters without proper authorization
  • Ignoring EMI sources during installation