HEIDENHAIN 231-E1A0 - E1A0 RDY.x status of axes stays inactive (safety relay)

E1A0 RDY.x status of axes stays inactive (safety relay)

During the safety-relay test, the -STO.A.G signals of the axes stayed at the active level even though the MC commanded the inactive state. A power stage of at least one feed or auxiliary axis remains locked by the safety signal.

Root Cause Summary

Alarm 231-E1A0 indicates the STO (Safe Torque Off) safety relay system is preventing axis power stages from becoming ready. The MC (Machine Control) cannot activate the RDY.x status because the -STO.A.G safety signals remain in an active state, keeping the inverter power stages locked.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Check safety relay status

    Navigate to MOD > DIAGNOSIS > MACHINE > I/O and verify the status of safety relay inputs X121.17 and X121.18 (-STO.A.G signals).

    These signals should show LOW (inactive) when safety circuit is closed

  2. 2

    Measure relay coil voltage

    Use multimeter to verify 24VDC supply to safety relay coil and check for proper switching operation when E-stop is cycled.

    Ensure machine is in safe state before measuring voltages

  3. 3

    Test relay contacts

    With power off, use ohmmeter to test continuity of safety relay NO/NC contacts and verify they switch properly when relay is energized/de-energized.

  4. 4

    Replace safety relay

    If relay shows signs of contact welding or coil failure, replace with identical part number and re-test STO circuit operation.

DIY Feasiblehigh confidence

Call a technician if:

  • ·TNC input card replacement required
  • ·Safety system validation needed after repairs
  • ·Parameter backup/restore required

Prevention

  • Regular safety relay contact inspection
  • Periodic STO circuit continuity testing
  • Keep spare safety relays in inventory
  • Document all safety parameter changes

Common Mistakes

  • Bypassing safety circuits for testing
  • Incorrect signal polarity configuration
  • Using non-safety rated relays
  • Ignoring intermittent connection issues