HEIDENHAIN 231-E220 - E220 Standstill monitoring SKERN-CC

E220 Standstill monitoring SKERN-CC

SKERN-CC standstill monitoring detected an axis movement larger than allowed while the drive was in the SOS safety state, even though the standstill speed was not exceeded. The permitted travel is set in machine parameter positionRangeVmin; other causes are brake/position-controller sequencing issues or a following error after axis locking.

Root Cause Summary

HEIDENHAIN alarm 231-E220 occurs when SKERN-CC safety monitoring detects excessive axis movement during standstill conditions, typically due to brake timing issues or incorrect MP positionRangeVmin parameter settings. The alarm triggers when axis movement exceeds the permitted range defined in machine parameter positionRangeVmin while in SOS (Safe Operating Stop) state.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Check brake timing parameters

    Access MOD function, select machine parameters, navigate to axis-specific parameters and verify MP7310 (brake activation delay) and MP7311 (brake release delay) settings.

    Typical values are 50-200ms for activation delay and 100-300ms for release delay depending on brake type.

  2. 2

    Monitor brake sequence in diagnostic mode

    Use TNC diagnostic screen (CTRL+DIAG) to observe brake output signals and position controller status during axis enable/disable cycles.

    Ensure machine is in safe condition before testing brake sequences.

  3. 3

    Adjust brake timing if necessary

    Increase MP7310 if brake activates too late, or increase MP7311 if brake releases too early, ensuring position controller is active before brake release.

    Make small incremental changes (25-50ms) and test each adjustment.

DIY Feasiblehigh confidence

Call a technician if:

  • ·Brake replacement required
  • ·Safety parameter changes needed
  • ·PLC programming modifications required

Prevention

  • Regular brake maintenance and testing
  • Proper machine parameter documentation
  • Periodic safety system validation
  • Environmental temperature monitoring

Common Mistakes

  • Increasing positionRangeVmin excessively without considering safety implications
  • Ignoring brake timing parameter relationships
  • Disabling standstill monitoring instead of fixing root cause