HEIDENHAIN 231-E033 - E033 CC FS outputs not "0" 64-95: 96-127
HEIDENHAIN alarm 231-E033 occurs when fail-safe (FS) outputs 64-127 remain active during the safety watchdog self-test cycle, indicating they failed to reset properly. This typically results from hardware short circuits to +24V, defective safety I/O modules, or corrupted safety configuration parameters in the TNC control.
HEIDENHAIN 231-E033 - E033 CC FS outputs not "0" 64-95: 96-127
E033 CC FS outputs not "0" 64-95: 96-127
During the watchdog test of the safety self-test, FS outputs 64-127 remained set although they should have been reset. A short circuit of an FS output to +24 V or a hardware defect is the likely cause.
Root Cause Summary
HEIDENHAIN alarm 231-E033 occurs when fail-safe (FS) outputs 64-127 remain active during the safety watchdog self-test cycle, indicating they failed to reset properly. This typically results from hardware short circuits to +24V, defective safety I/O modules, or corrupted safety configuration parameters in the TNC control.
Safety
Causes and Fixes
Identify Affected FS Outputs
Check alarm parameters %4 and %5 to decode which specific FS outputs 64-127 are stuck high. Convert hex values to binary to identify individual output bits.
Use TNC calculator function (CALC key) to convert hex alarm parameters to binary for easier bit identification
Disconnect External Wiring
Power down system and disconnect all external wiring from the identified FS output terminals on the safety I/O modules.
Follow LOTO procedures - safety system must be completely de-energized before disconnecting FS outputs
Test Output Isolation
Power up control and check if alarm clears. If cleared, short circuit is in external wiring. If alarm persists, internal hardware fault exists.
Use TNC diagnostic screen MOD → Diagnosis → I/O to monitor FS output states in real-time
Measure Output Voltages
With outputs disconnected, measure voltage on affected FS output terminals. Should read 0V when output commanded off during watchdog test.
Use CAT III rated multimeter - FS outputs can carry significant current when shorted
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.