Heidenhain Controller
System · Intermediate · 30-120 minutes
HEIDENHAIN 231-E02C - E02C SKERN-CC: Dynamisierungtest ES.B fehlerhaft
The Heidenhain 231-E02C alarm typically results from a failure in the dynamic test of PLC peripheral devices, often due to an inactive or defective ES.B input. The most common issues are wiring errors in test groups or test outputs, or errors in the configuration file (IOC file). The most likely fix involves checking and correcting the wiring or configuration settings of the HSCI system.
HEIDENHAIN 231-E02C - E02C SKERN-CC: Dynamisierungtest ES.B fehlerhaft
E02C SKERN-CC: Dynamisierungtest ES.B fehlerhaft
The dynamic test of the PLC peripheral devices found that an ES.B input was not activated or is defective. Wiring errors of the test groups/outputs or an error in the IOC configuration file are the likely reasons.
Root Cause Summary
The Heidenhain 231-E02C alarm typically results from a failure in the dynamic test of PLC peripheral devices, often due to an inactive or defective ES.B input. The most common issues are wiring errors in test groups or test outputs, or errors in the configuration file (IOC file). The most likely fix involves checking and correcting the wiring or configuration settings of the HSCI system.
Safety
Causes and Fixes
Inspect Wiring Connections
Visually inspect all wiring connections related to the test groups and test outputs for loose, disconnected, or damaged cables. Focus on the ES.B input connections to the PLC peripheral devices.
Use a flashlight to check for subtle damage or corrosion on connectors that might not be visible under normal lighting.
Ensure the machine is powered off and locked out before inspecting wiring to avoid electrical shock.
Test Wiring Continuity
Use a multimeter set to continuity mode to test the wiring between the ES.B input and the corresponding test output. Check for breaks or shorts in the circuit.
Label each wire before testing to avoid confusion when reconnecting, especially in complex setups.
Double-check multimeter settings to avoid applying voltage to the circuit during testing.
Repair or Replace Damaged Wiring
If continuity tests reveal breaks or shorts, repair the wiring by splicing and insulating damaged sections or replace the entire cable if damage is extensive. Re-test after repairs.
Use heat-shrink tubing for durable insulation on spliced wires to prevent future failures.
Ensure all repairs comply with Heidenhain wiring standards to avoid further issues.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.