Communication · Intermediate · 30-120 minutes
Heidenhain 231-C690 - C690 DQ communication error
The C690 alarm is fundamentally a breakdown in the digital communication protocol between the TNC control and the drive system. This occurs when the control cannot establish or maintain reliable data exchange with the drive module, preventing proper servo control. The issue is almost always hardware-related, involving cabling, connectors, power supply integrity, or drive electronics failure rather than software configuration.
Heidenhain 231-C690 - C690 DQ communication error
C690 DQ communication error
This alarm indicates a communication error on the DriveQ (DQ) digital drive interface between the Heidenhain TNC control and one or more axis drives. The parameter typically identifies the specific axis or drive module experiencing the communication fault. This is a critical error that prevents proper command transmission to the servo drives over the EnDat or digital interface.
Root Cause Summary
The C690 alarm is fundamentally a breakdown in the digital communication protocol between the TNC control and the drive system. This occurs when the control cannot establish or maintain reliable data exchange with the drive module, preventing proper servo control. The issue is almost always hardware-related, involving cabling, connectors, power supply integrity, or drive electronics failure rather than software configuration.
Safety
Causes and Fixes
Identify Affected Axis
Note the axis designation from the %1 parameter in alarm 231-C690. Cross-reference this with the machine's electrical documentation to locate the specific drive module and cable routing.
The %1 parameter often shows the logical axis name (X, Y, Z, etc.) but may show the physical drive number depending on TNC version.
Inspect Cable Connections
Power down the control and check the EnDat/drive communication cable at both ends - X116/X126 connectors on the TNC side and the corresponding connector on the drive module. Look for bent pins, contamination, or loose retention clips.
Always disconnect main power and wait for DC-Bus discharge (minimum 5 minutes) before handling drive connections.
Check Cable Routing and Condition
Inspect the cable along its entire length for pinch points, sharp bends (minimum bend radius 10x cable diameter), or proximity to power cables. Check cable shields are properly terminated at both ends.
Drive communication cables should never be routed in the same cable tray as motor power cables - maintain minimum 200mm separation.
Perform Cable Swap Test
If possible, swap the suspected cable with an identical cable from a functioning axis. If the alarm follows the cable, replace it. Use only Heidenhain-approved shielded cables with correct impedance.
Always use cables with part numbers specified in the drive system documentation - generic industrial cables often lack the required electrical characteristics.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.