Heidenhain codes
HeidenhainParameterIntermediate30-120 minutes

231-9260

HEIDENHAIN 231-9260 - 9260 Motor parameters changed

9260 Motor parameters changed

This TNC 640 error indicates invalid machine parameter settings. The control has detected configuration data that does not match the hardware setup.

Root Cause Summary

Alarm 231-9260 occurs when motor parameters are modified in the drive configuration while the servo drive remains powered on. The Heidenhain TNC system requires a complete drive power cycle to properly initialize new motor parameters and prevent servo instability.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Access machine parameters

    Press MOD key, select 'Machine Parameters', navigate to MP72xx series motor parameters for the affected axis.

    Always document original parameter values before making changes

  2. 2

    Verify motor parameter changes

    Check MP7210 (motor type), MP7220 (rated motor speed), MP7230 (rated motor current) for recent modifications.

    Never change motor parameters while machine is in automatic mode

  3. 3

    Execute complete drive shutdown

    Turn off main power, wait 30 seconds for capacitor discharge, then power up system to reinitialize motor parameters.

    Use controlled shutdown via PLC rather than emergency stop for clean parameter reset

  4. 4

    Perform axis reference

    Execute reference run for affected axis using Manual mode, verify smooth operation and proper following error limits.

    Check axis movement at reduced feedrate initially

DIY Feasiblehigh confidence

Call a technician if:

  • ·Parameter transfer repeatedly fails
  • ·Servo amplifier hardware fault suspected
  • ·Motor encoder damage indicated

Prevention

  • Always power down drives before motor parameter changes
  • Document all parameter modifications
  • Use parameter backup before changes
  • Follow proper startup sequence after parameter modifications

Common Mistakes

  • Changing parameters during production
  • Skipping drive power cycle
  • Not verifying parameter transfer completion
  • Ignoring encoder-motor parameter consistency