HEIDENHAIN 231-9300 - 9300 Field angle determination not allowed
Alarm 231-9300 occurs when the TNC control attempts to perform field angle determination using an incompatible method or encoder configuration. This typically happens during servo commissioning or when encoder parameters are incorrectly configured for the selected field angle determination method.
HEIDENHAIN 231-9300 - 9300 Field angle determination not allowed
9300 Field angle determination not allowed
This TNC 640 error indicates the drive cannot determine the correct field angle for motor commutation. The control lacks necessary rotor position information.
Root Cause Summary
Alarm 231-9300 occurs when the TNC control attempts to perform field angle determination using an incompatible method or encoder configuration. This typically happens during servo commissioning or when encoder parameters are incorrectly configured for the selected field angle determination method.
Safety
Causes and Fixes
Check encoder type configuration
Navigate to MOD > Machine Parameters > MP710 POSITION_MEASURING_SYSTEM and verify encoder type matches physical encoder installed.
Use MP711 to confirm encoder interface type (EnDat, SSI, incremental) matches your actual encoder
Verify field angle determination method
Check MP750 FIELD_ANGLE_DETERMINATION method - ensure it's compatible with your encoder type (0=disabled, 1=with encoder, 2=without encoder).
Never attempt field angle determination with incremental encoders using method 1
Reconfigure parameters if mismatch found
If encoder is incremental, set MP750=2 or 0. If absolute encoder, verify MP712-MP715 encoder resolution parameters match encoder specifications.
Always cycle power after changing encoder-related machine parameters
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.