HEIDENHAIN 126-0111 - Too many switch-off ports defined
The TNC control has a hardware and software limitation on the number of digital outputs that can be designated as switch-off ports for safety functions. This alarm indicates the configuration exceeds this limit, typically due to excessive or duplicate assignments in the PLC program or machine parameters. The specific limit varies by control model and hardware configuration.
HEIDENHAIN 126-0111 - Too many switch-off ports defined
Too many switch-off ports defined
The IOC file defines more than one output for switching the machine off after shutdown, which is not permitted. Only a single output may be assigned to this function.
Root Cause Summary
The TNC control has a hardware and software limitation on the number of digital outputs that can be designated as switch-off ports for safety functions. This alarm indicates the configuration exceeds this limit, typically due to excessive or duplicate assignments in the PLC program or machine parameters. The specific limit varies by control model and hardware configuration.
Safety
Causes and Fixes
Enter parameter programming mode
Press MOD key, enter password if required, select 'Machine Parameters' from the menu. Navigate to parameter group MP7310.x (Emergency Stop Configuration).
Do not modify safety-related parameters without proper authorization and documentation. Incorrect changes can compromise machine safety.
Document current switch-off port configuration
Record all entries in MP7310.0 through MP7310.15 (or applicable range). Note which physical outputs (X1xx) are assigned as switch-off ports. Count total assignments.
Use TNCguide documentation for your specific control model to verify maximum allowed switch-off ports - typically 4 for TNC 320, 6-8 for TNC 530/620/640.
Identify redundant or unnecessary assignments
Review machine safety circuit design to determine which outputs are truly required for emergency stop functions. Look for duplicate assignments or test outputs that should not be safety-rated.
Switch-off ports are typically reserved for safety contactors, brake releases, and spindle motor disconnects. Ancillary equipment like coolant or chip conveyors should use standard outputs.
Remove excessive assignments
Delete entries from MP7310.x parameters that exceed the limit or are non-essential. Ensure remaining assignments match physical safety circuit design. Save parameters and perform a control restart.
Verify safety circuit integrity after parameter changes. Test emergency stop function before returning machine to production.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.