FANUC Alarm SV3 - Low DC Link Voltage (LVDC)
The FANUC Alarm SV3 - Low DC Link Voltage (LVDC) is most commonly caused by issues with the Alpha Power Supply Module (PSM) or insufficient AC input power. The most likely fix involves diagnosing and resolving PSM alarms or correcting input power issues. If these are not the issue, internal servo amplifier faults may be the culprit.
FANUC Alarm SV3 - Low DC Link Voltage (LVDC)
Low DC Link Voltage LVDC
The DC bus voltage inside the Fanuc Alpha servo amplifier has dropped below the minimum operating level. The DC link is charged by the Alpha power supply module (PSM) and powers the servo motor drive circuits. This alarm indicates the power supply module is not providing sufficient DC bus voltage.
Root Cause Summary
The FANUC Alarm SV3 - Low DC Link Voltage (LVDC) is most commonly caused by issues with the Alpha Power Supply Module (PSM) or insufficient AC input power. The most likely fix involves diagnosing and resolving PSM alarms or correcting input power issues. If these are not the issue, internal servo amplifier faults may be the culprit.
Causes and Fixes
Check PSM LED Display for Alarms
Power down the machine safely and inspect the LED display on the PSM for any alarm codes. Refer to the FANUC PSM manual to decode the alarm and follow specific troubleshooting for that code.
Take a photo of the LED display for reference in case the alarm clears unexpectedly.
Ensure machine power is off and locked out before accessing the PSM to avoid electrical shock.
Verify PSM Output Voltage
If no alarm is present, use a multimeter set to DC voltage mode to measure the output at the PSM DC bus terminals. Compare the reading to the expected range (280-325VDC for 200V class, 560-650VDC for 400V class).
Use insulated probes rated for high voltage to ensure accurate readings and safety.
High voltage present; only trained personnel should perform this measurement.
Reset or Replace PSM if Necessary
If an alarm is present or output voltage is out of spec, attempt a power cycle reset of the PSM. If the issue persists, document the alarm code and prepare to replace the PSM with a compatible unit.
Keep a spare PSM on hand for critical machines to minimize downtime during failures.
Do not bypass PSM alarms; this can lead to further damage.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.