Fanuc spindle alarm 575: SPINDLE COOLANT TEMPERATURE ERROR. The spindle drive or spindle motor has detected a fault condition that requires diagnosis before spindle operation can resume.

Root Cause Summary

Alarm 575 indicates the spindle coolant temperature has exceeded safe operating limits or the temperature monitoring system has failed. This occurs when the coolant circulating through the spindle motor is too hot, flow is restricted, or temperature sensors/wiring have failed. The alarm protects the spindle motor from thermal damage by shutting down operation.

Safety

  • Verify corrected program or parameters before resuming machining

Causes and Fixes

  1. 1

    Check coolant flow rate at the spindle motor inlet and outlet connections. Verify flow meets manufacturer specifications (typically 15-25 liters/minute for most spindles).

  2. 2

    Inspect heat exchanger operation. Check coolant inlet temperature (should be 15-20°C), verify chiller compressor is running, and check for clogged heat exchanger fins or internal passages.

  3. 3

    Examine coolant filter and clean or replace if clogged. Check all coolant lines for kinks, blockages, or debris restricting flow.

    Ensure machine power is off before disconnecting coolant lines to prevent spills.

  4. 4

    Verify coolant pump is operating at correct pressure (typically 2-4 bar). Listen for abnormal pump noise indicating cavitation or bearing failure.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.