Fanuc Alarm 431 - Converter Unit Overheat
Alarm 431 CNV. OVERLOAD indicates thermal overload protection has triggered in the converter section of the PSM (Power Supply Module) or beta/αi series SVU (Servo Unit). This occurs when internal temperature exceeds safe operating limits due to inadequate cooling, excessive load cycling, or environmental factors. The alarm protects power conversion electronics from thermal damage.
Fanuc Alarm 431 - Converter Unit Overheat
CNV Overheat
Thermal protection alarm activated. The cnv overheat has exceeded safe operating temperature and requires immediate attention to prevent component damage.
Root Cause Summary
Alarm 431 CNV. OVERLOAD indicates thermal overload protection has triggered in the converter section of the PSM (Power Supply Module) or beta/αi series SVU (Servo Unit). This occurs when internal temperature exceeds safe operating limits due to inadequate cooling, excessive load cycling, or environmental factors. The alarm protects power conversion electronics from thermal damage.
Safety
Causes and Fixes
Power down the system and inspect all cooling fans on PSM and servo amplifier units for rotation and airflow. Check for fan LED indicators on amplifier front panel (steady green = normal, red/off = fan fault).
Allow 5 minutes after power-down for capacitor discharge before opening cabinet doors.
Remove and clean/replace air intake filters on control cabinet. Inspect exhaust vents and internal air passages for dust accumulation or obstructions. Verify minimum 100mm clearance around PSM/SVU units.
Check ambient temperature inside control cabinet using SYSTEM > DIAGNOSIS > SERVO screen and verify parameter 8901#0 (temperature monitoring enable) is set to 1. Review diagnosis numbers 400-407 for servo amplifier temperatures (should be below 55°C).
Verify cabinet ambient temperature is within specification (0-45°C for most αi/β series). Install additional ventilation or air conditioning if cabinet consistently exceeds 40°C during operation.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.