Siemens SINUMERIK codes
Siemens SINUMERIKServo/AxisIntermediate20-45 minutes

61418

Siemens 840D 61418 - Channel block: Protocol file too small, check MD11420

Channel block: Protocol file too small, check MD11420

Alarm can be triggered by following measuring cycle: CYCLE106 Remedy: Check MD11420: LEN_PROTOCOL_FILE.

Safety

  • Refer to Siemens documentation
  • Ensure qualified technician performs repairs

Common Causes

  • MD11420 (LEN_PROTOCOL_FILE) parameter set too small for measurement data being generated
  • CYCLE106 measuring cycle generating more data than allocated buffer size
  • Protocol file memory allocation insufficient for active measurement operations
  • Corrupted or incomplete parameter configuration after system update or reset
  • Multiple simultaneous measurement cycles exceeding available protocol buffer capacity

Troubleshooting Steps

  1. 1Verify current MD11420 parameter value and compare against actual protocol file requirements for CYCLE106 execution
  2. 2Review measurement cycle complexity and data output volume; increase MD11420 buffer size incrementally (typical range 4KB-64KB depending on application)
  3. 3Clear existing protocol files and reset measurement cycle to baseline parameters, then re-execute CYCLE106 with increased MD11420 value
  4. 4Check for parameter backup and restore defaults if configuration appears corrupted; reconfigure MD11420 to accommodate measurement data size
  5. 5Monitor protocol file growth during CYCLE106 execution using Diagnostics menu; adjust MD11420 to 150% of observed maximum if alarm persists