Siemens 840D 4630 - Invalid handwheel module for handwheel
Alarm 4630 indicates a configuration mismatch in the handwheel module setup where $MN_HANDWHEEL_MODULE references a handwheel entry that does not have a corresponding valid entry in the $MN_HANDWHEEL_LOGIC_ADDRESS[] array. This prevents the NCK from establishing the PROFIBUS handwheel logical address mapping required for jog pendant operation.
Siemens 840D 4630 - Invalid handwheel module for handwheel
Invalid handwheel module for handwheel
Siemens SINUMERIK 840D system notice 4630: Invalid handwheel module for handwheel. This is a system-level notification regarding machine data or configuration. Note the message details and take the indicated action.
Root Cause Summary
Alarm 4630 indicates a configuration mismatch in the handwheel module setup where $MN_HANDWHEEL_MODULE references a handwheel entry that does not have a corresponding valid entry in the $MN_HANDWHEEL_LOGIC_ADDRESS[] array. This prevents the NCK from establishing the PROFIBUS handwheel logical address mapping required for jog pendant operation.
Safety
Causes and Fixes
Navigate to Diagnostics > Parameters > Machine Data (MD) and locate $MN_HANDWHEEL_MODULE. Note the module index value (e.g., 1).
Check $MN_HANDWHEEL_LOGIC_ADDRESS[index] where index matches the module number from step 1. Verify the array element contains a valid PROFIBUS logical address (typically 0-125). If the element is empty, zero, or contains 255 (invalid marker), the entry is missing.
An address value of 255 or -1 indicates the entry was never configured.
If the array entry is missing, assign a valid PROFIBUS logical address using HMI > Service > Machine Data, or edit via SINUMERIK Operate. Coordinate with your PROFIBUS master configuration to ensure no address conflicts.
After correction, perform a warm restart (Diagnostics > System > Restart) or full power cycle to reload NCK parameter tables and verify alarm 4630 clears.
Changes to handwheel PROFIBUS addressing require system restart; online changes alone will not resolve this alarm.
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.