Siemens SINUMERIK codes
Siemens SINUMERIKCommunicationIntermediate30-120 minutes

4702

Siemens 4702 - PROFIBUS I/O: The logical slot / I/O area address was not found.

PROFIBUS I/O: The logical slot / I/O area address was not found.

For PROFIBUS/PROFINET only: The logical slot / I/O area address was not found in MD10506 $MN_DPIO_LOGIC_ADDRESS_OUT with the stated slot / I/O area index in the current STEP 7 hardware configuration Control reaction: Interface signals are set. Alarm display.

Root Cause Summary

Alarm 4702 fires when the NCK cannot locate a PROFIBUS I/O logical slot address that has been referenced in the part program or PLC, but is not configured in machine data MD10506 ($MN_DPIO_LOGIC_ADDRESS_OUT). This indicates a mismatch between the I/O addressing table in the control system and the actual PROFIBUS device configuration or mapping.

Safety

  • Only qualified personnel should diagnose and clear control alarms; follow the machine builder's safety procedures and lockout/tagout where hardware work is required.

Causes and Fixes

  1. 1

    Access Siemens SINUMERIK HMI or SCOUT software and navigate to Parameterization > Machine Data > Axis/Spindle > PROFIBUS I/O Configuration. Locate MD10506 ($MN_DPIO_LOGIC_ADDRESS_OUT).

  2. 2

    Review the slot index value from the alarm message (%1 parameter). Cross-reference this index against all entries configured in MD10506. Verify that the slot exists and contains a valid logical address mapping.

    If the index is beyond the configured array bounds, the entry is missing.

  3. 3

    Check the NC program (.mpf or .spf file) and PLC program for references to the missing slot address. Use the Siemens editor to search for PROFIBUS write operations or I/O area calls matching the slot index.

  4. 4

    Add the missing logical address entry to MD10506 or update the existing entry with the correct PROFIBUS slave node ID and I/O area offset. After modification, perform a cold restart (POWER OFF > wait 10s > POWER ON) to reload machine data.

    Changes to PROFIBUS mapping require system restart; do not attempt online modification during cycle.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.