Siemens 27030 - Axis function not supported on this 611D module
Alarm 27030 fires when SINUMERIK Safety Integrated functions are activated without a 611D Performance module installed that supports dual measuring circuits and safety cutoff relay. This mismatch between safety function configuration and actual drive hardware causes the NCK to reject the safety command during axis initialization or safety function activation.
Siemens 27030 - Axis function not supported on this 611D module
Axis function not supported on this 611D module
SINUMERIK Safety Integrated can be used only with the 611D Performance control modules with 2 measuring circuits per drive and cutoff relay. An attempt has been made to activate a safety function although no such module is plugged in Control reaction: Mode group not ready. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm.
Root Cause Summary
Alarm 27030 fires when SINUMERIK Safety Integrated functions are activated without a 611D Performance module installed that supports dual measuring circuits and safety cutoff relay. This mismatch between safety function configuration and actual drive hardware causes the NCK to reject the safety command during axis initialization or safety function activation.
Safety
Causes and Fixes
Power down the machine and physically verify the installed drive modules in the cabinet. Check the module label for '611D Performance' (includes dual encoder inputs and safety relay module).
Verify system is in safe state and all servo power is discharged before accessing cabinet.
Access Diagnostics > Hardware Configuration in HMI or NCK menu. Verify the detected module type matches the physical hardware. If mismatch exists, re-seat the module and perform a system restart.
If Standard module is confirmed, either replace with 611D Performance module or disable safety functions by clearing MD 30380 (SsiActivateAxis) = 0 for the affected axis.
Replacing drive modules requires re-commissioning of axis tuning parameters (MD 32010-32020 velocity/acceleration gains).
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.