axismd.ai
Siemens SINUMERIK Controller
Servo/Axis · Intermediate · 30-120 minutes
Siemens 25042 - Axis standstill monitoring during torque/force limitation
Alarm 25042 indicates that an axis failed to reach its commanded end position within the standstill monitoring time window while operating under torque or force limitation. This occurs when the NCK detects that axis motion has ceased before the target position was achieved, typically due to mechanical blockage, insufficient drive torque, or improperly configured monitoring parameters.
Siemens 25042 - Axis standstill monitoring during torque/force limitation
Axis standstill monitoring during torque/force limitation
The defined end position was not reached within the time specified in the machine data Control reaction: Mode group not ready. The NC switches to follow-up mode. Channel not ready. NC Start disable in this channel. Interface signals are set. Alarm display. NC Stop on alarm. Channel not ready.
Root Cause Summary
Alarm 25042 indicates that an axis failed to reach its commanded end position within the standstill monitoring time window while operating under torque or force limitation. This occurs when the NCK detects that axis motion has ceased before the target position was achieved, typically due to mechanical blockage, insufficient drive torque, or improperly configured monitoring parameters.
Safety
Causes and Fixes
Access Diagnostics > Axes > [Axis Name] > Parameters and verify MD32100 (Force Limitation Enable) status and MD32102-MD32105 (axis force limit setpoints). Compare against machine specification sheets for nominal torque/force ratings.
Do not increase force limits beyond machine mechanical specifications without engineering review.
In the NC program, check for G-code blocks with FMAX or FLIN declarations that may override default MD values. Verify these values are appropriate for the workpiece material and mechanical setup.
Increase the force limit incrementally (MD32102-MD32105) in 5-10% steps and re-execute the positioning cycle while monitoring actual axis load in Diagnostics > Measured Data > Drive Current.
If force limit is already at specification and alarm persists, escalate to mechanical inspection (backlash, wear, binding).