Heidenhain codes
HeidenhainSafetyIntermediate30-120 minutes

330-0003

HEIDENHAIN 330-0003 - External EMERGENCY STOP

External EMERGENCY STOP

A PLC configuration or communication error has been detected. This affects the interaction between the control and the PLC system.

Root Cause Summary

HEIDENHAIN alarm 330-0003 occurs when the PLC input for the control-ready signal becomes inactive, typically due to an interrupted emergency stop circuit or external safety interlock. This safety-critical alarm prevents machine operation until the emergency stop condition is cleared and the safety circuit is properly restored.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Visual E-Stop Inspection

    Check all emergency stop buttons on machine panel, operator pendant, and remote stations for engaged (twisted/pulled) position.

    Never bypass emergency stops - they are critical safety devices

  2. 2

    Reset E-Stop Buttons

    Twist clockwise or push to release all emergency stop buttons. Ensure buttons return to normal (raised) position with audible click.

    Some older machines require specific sequence - main panel first, then pendant

  3. 3

    Verify PLC Input Status

    Access PLC menu via MOD function, select 'PLC Status' and check X121.1 or configured E-stop input shows '1' (active high) after reset.

    Input assignment may vary - check machine parameter MP7300.x for actual E-stop input mapping

  4. 4

    Clear Alarm and Test

    Press CE key to clear alarm, then test E-stop function by activating and releasing to ensure proper operation.

DIY Feasiblehigh confidence

Call a technician if:

  • ·PLC program modifications needed
  • ·Safety relay replacement required
  • ·Electrical panel work beyond basic checks

Prevention

  • Regular E-stop button testing monthly
  • Keep safety switches clean and properly adjusted
  • Monitor 24VDC supply voltage regularly
  • Document all safety circuit modifications

Common Mistakes

  • Bypassing safety devices temporarily
  • Ignoring intermittent E-stop issues
  • Not testing all E-stop buttons after maintenance
  • Assuming alarm is always hardware related without checking PLC logic

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.