HEIDENHAIN 239-0111 - 111 CC-FSUC: voltage error CC
This alarm is triggered when the CC axis module's internal voltage monitoring detects that supply voltages have deviated outside acceptable operating ranges. The root cause is typically either inadequate DC bus voltage supply from the main power section, localized voltage regulation failure within the CC module itself, or poor electrical connections causing voltage drops under load conditions.
HEIDENHAIN 239-0111 - 111 CC-FSUC: voltage error CC
111 CC-FSUC: voltage error CC
This safety-related error indicates a fault in the FS microcontroller. Voltage monitoring reports an error. The control has detected a safety issue that may affect safe operation.
Root Cause Summary
This alarm is triggered when the CC axis module's internal voltage monitoring detects that supply voltages have deviated outside acceptable operating ranges. The root cause is typically either inadequate DC bus voltage supply from the main power section, localized voltage regulation failure within the CC module itself, or poor electrical connections causing voltage drops under load conditions.
Safety
Causes and Fixes
Access CC Voltage Diagnostics
Press MOD key > DIAGNOSIS > CC > select the CC module indicated in %2 parameter. Observe the 'DC Bus Voltage' real-time value. Nominal value should be 540-750V for 3x480V systems, 270-375V for 3x230V systems.
Record the voltage value during normal operation and during axis motion to identify dynamic voltage drops that only occur under load.
Check Power Supply Unit Output
Measure DC bus voltage directly at the PSU output terminals using a multimeter set to DC voltage range >800V. Compare with the CC module's reported value to verify measurement accuracy.
High voltage present. Use CAT III rated test equipment and appropriate PPE. Lock out main power before accessing terminals.
Verify Line Reactor and Pre-Charge
Check that the line reactor (if equipped) is properly connected and not shorted. Verify the DC bus pre-charge circuit completes before drive enable by observing the pre-charge contactor timing.
A failing pre-charge resistor or relay can cause insufficient initial voltage that drops further under load.
Review Simultaneous Axis Loading
Examine the NC program or PLC sequence for simultaneous high-acceleration moves on multiple axes. Check if alarm correlates with specific motion patterns using the Error Memory timestamp.
Modify MP1010 (axis-specific current limits) to reduce peak power demand if undersized power supply is confirmed.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.