axismd.ai
Heidenhain Controller
Servo/Axis · Intermediate · 30-120 minutes
Heidenhain 231-806B - 806B Powerfail AC drive cntrller
This alarm specifically indicates that the AC drive controller has detected a power failure condition in its internal DC bus voltage monitoring circuit. The Heidenhain TNC receives this fault status from the drive controller via the digital drive interface, triggering the 806B alarm to prevent machine motion during unsafe power conditions.
Heidenhain 231-806B - 806B Powerfail AC drive cntrller
806B Powerfail AC drive cntrller
Alarm 806B indicates a power failure detected by the AC drive controller (inverter module) that supplies power to the spindle or axis drives. This alarm occurs when the control detects a loss or significant drop in the DC bus voltage within the drive controller, typically due to incoming AC line power interruption or DC bus voltage collapse below the operational threshold.
Root Cause Summary
This alarm specifically indicates that the AC drive controller has detected a power failure condition in its internal DC bus voltage monitoring circuit. The Heidenhain TNC receives this fault status from the drive controller via the digital drive interface, triggering the 806B alarm to prevent machine motion during unsafe power conditions.
Safety
Causes and Fixes
Verify AC Input Voltage Stability
Using a true-RMS multimeter or power quality analyzer, measure all three phases (L1, L2, L3) at the main disconnect feeding the drive controller cabinet. Verify voltage is within 380-420VAC for 400V systems or 440-480VAC for 460V systems. Check for phase imbalance greater than 2%.
Use the multimeter's MIN/MAX recording function over several minutes to catch intermittent voltage sags that may not be obvious during spot checks.
Only qualified electricians should work inside the main electrical cabinet. Lethal voltages are present.
Check Building Power Quality
Consult with facility maintenance to identify if other equipment experienced power disruptions at the same time. Check for heavy loads on the same circuit (welders, large motors) that could cause voltage sags during startup.
806B alarms occurring at consistent times (morning startup, shift changes) often point to facility-wide power quality issues rather than machine-specific faults.
Inspect Main Contactor and Circuit Breakers
With power OFF, inspect the main line contactor (typically labeled K1 or similar) for contact wear, pitting, or burn marks. Check all circuit breakers for loose mounting or internal failure. Verify proper torque on all AC input terminals per manufacturer specifications.
Use proper lockout/tagout procedures before opening any electrical panels.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.