Heidenhain codes
HeidenhainPower SupplyIntermediate30-120 minutes

231-8060

HEIDENHAIN 231-8060 - 8060 Leakage current in UV 1xx

8060 Leakage current in UV 1xx

This TNC 640 error indicates excessive current draw in the drive system. The control has detected overload conditions that could damage the motor or inverter.

Root Cause Summary

HEIDENHAIN alarm 231-8060 indicates excessive leakage current detected in the UV inverter module, typically caused by insulation breakdown in the motor windings or contamination in the drive system. The TNC control monitors ground fault currents through the inverter's integrated safety circuits and triggers this alarm when leakage exceeds safe thresholds.

Safety

  • Refer to Heidenhain service manual
  • Ensure qualified technician performs repairs

Causes and Fixes

  1. 1

    Access drive diagnostics

    Navigate to MOD function → Service → Drive diagnosis → Select affected UV axis to view insulation resistance values.

    Check historical drive data logs for gradual insulation degradation trends

  2. 2

    Perform insulation resistance test

    Power down system, disconnect motor cables at inverter, use megohmmeter to test phase-to-ground resistance (should be >10MΩ).

    Ensure complete power isolation and discharge capacitors before testing

  3. 3

    Check motor parameters

    Verify motor data in machine parameter MP7xx series matches actual motor specifications, particularly insulation class and rated voltage.

    Compare current motor parameters with original commissioning documentation

  4. 4

    Inspect motor physically

    Check motor housing for moisture ingress, damaged cable entries, or signs of overheating that could cause insulation breakdown.

    Look for burn marks or unusual odors indicating thermal damage

Service Recommendedmedium confidence

Call a technician if:

  • ·Insulation resistance below 1MΩ
  • ·Multiple axes showing similar symptoms
  • ·Ground fault detection circuit failure
  • ·Contamination source cannot be identified

Prevention

  • Regular insulation resistance testing
  • Maintain proper environmental sealing
  • Implement preventive cable inspection schedule
  • Monitor drive diagnostic logs for trending

Common Mistakes

  • Ignoring gradual insulation degradation
  • Using incorrect cable types during replacement
  • Disabling ground fault protection instead of fixing root cause
  • Not addressing contamination source after cleaning