Haas Alarm 1321 - Coolant Pump Thermal
Alarm 1321 occurs when the coolant pump motor thermal overload relay trips due to excessive current draw or overheating. This protective relay monitors motor amperage and temperature, opening the contactor when preset limits are exceeded to prevent motor damage.
Haas Alarm 1321 - Coolant Pump Thermal
Coolant Pump Thermal
This alarm indicates the coolant pump motor has exceeded its thermal limit and the thermal overload relay has tripped to protect the motor from damage. The MOCON board receives a signal from the overload relay that the pump motor is overheating and immediately shuts down coolant flow. The machine can continue running in dry mode but coolant cannot be activated until the motor cools and the alarm is cleared.
Root Cause Summary
Alarm 1321 occurs when the coolant pump motor thermal overload relay trips due to excessive current draw or overheating. This protective relay monitors motor amperage and temperature, opening the contactor when preset limits are exceeded to prevent motor damage.
Safety
Causes and Fixes
Check overload relay status
Open electrical cabinet and locate the coolant pump motor starter. Check if the thermal overload relay reset button has popped out or shows a tripped indication.
Ensure machine is powered down and locked out before opening electrical cabinet.
Allow cooling time
Wait 10-15 minutes for the thermal overload relay to cool down before attempting reset. The relay must return to ambient temperature to reset properly.
Feel the motor housing - if it's hot to touch, allow additional cooling time.
Reset overload relay
Press the reset button on the thermal overload relay firmly until it clicks. Power up machine and test coolant pump operation from COOLNT button on control panel.
Monitor motor current
Use clamp meter to measure motor current during operation. Compare readings to motor nameplate amperage - should not exceed 110% of rated current.
Call a technician if:
Prevention
Common Mistakes