Haas Alarm 1 (Low Battery) occurs when the backup battery voltage drops below the minimum threshold required to maintain NVRAM memory and real-time clock functions. This alarm typically indicates the internal lithium battery needs replacement or has failed completely.
HaasPower SupplyBasic15-30 minutes
1
Haas Alarm 1 - Encoder Battery Low
Low Battery
This alarm indicates the absolute encoder battery voltage on the MOCON board has dropped below acceptable levels, typically below 3.0 VDC. The battery maintains machine position data when the control is powered off, and low voltage will result in loss of home position reference. The machine will require a re-home cycle after the alarm is cleared, and continued operation without replacing the battery risks losing machine zero at every power cycle.
Root Cause Summary
Haas Alarm 1 (Low Battery) occurs when the backup battery voltage drops below the minimum threshold required to maintain NVRAM memory and real-time clock functions. This alarm typically indicates the internal lithium battery needs replacement or has failed completely.
Safety
Position data at risk
Replace within 24 hours
Causes and Fixes
1
Check Battery Voltage Display
Press CURRENT COMMANDS, then navigate to DIAGNOSTICS > BATTERY to view current battery voltage. Normal voltage should read 3.0V or higher.
Document the voltage reading for service records
2
Power Down and Replace Battery
Turn off main power and disconnect AC power. Remove control panel cover and locate the lithium battery (usually CR2032 or equivalent). Replace with identical battery type.
Always power down completely before battery replacement to prevent data corruption
3
Restore Parameters and Clear Alarm
Power up the control, reload machine parameters from backup, reset clock via SETTING 7 (TIME), and press RESET to clear alarm 1.
Always have current parameter backup before battery replacement
1
Inspect Battery Holder
Power down and remove control cover. Visually inspect battery holder for corrosion, bent contacts, or loose mounting.
Ensure main power is off before opening control panel
2
Clean and Reseat Battery
Remove battery, clean contacts with isopropyl alcohol and fine abrasive pad. Check battery holder spring tension and reseat battery firmly.
Slightly bend battery holder contacts if spring tension is weak
3
Verify Connection and Test
Power up control and check DIAGNOSTICS > BATTERY voltage reading. Cycle power several times to verify stable connection.
Monitor voltage over several power cycles to confirm stable connection
1
Verify New Battery Voltage
Install known good battery and check voltage reading in DIAGNOSTICS > BATTERY. If voltage shows low with new battery, suspect board-level failure.
Test battery voltage with multimeter before installation to confirm it's good
2
Check for Board Damage
Inspect control board around battery circuit for burned components, corrosion, or physical damage. Look for swollen capacitors near NVRAM chips.
Do not attempt board-level repairs - this requires factory service
3
Document and Schedule Service
Record all voltage readings and visual observations. Contact Haas service for control board evaluation and potential replacement.
Have machine serial number and control software version ready for service call
1
Check Battery Voltage Reading
Navigate to DIAGNOSTICS > BATTERY and verify actual voltage reading. If voltage shows normal (>3.0V) but alarm persists, suspect parameter corruption.
Compare voltage reading with multimeter measurement across battery terminals
2
Restore Factory Parameters
Load factory default parameters via SETTING 84 (PARAMETER RESTORE) or reload from known good backup to restore proper alarm thresholds.
Save current parameters before restoration in case machine-specific settings are needed
3
Verify Alarm Clearance
After parameter restoration, cycle power and verify alarm 1 clears with proper battery voltage reading in diagnostics.
Re-enter any custom parameters after confirming alarm clearance