FANUC Robot codes
FANUC RobotServo/AxisIntermediate15-60 minutes

SRVO-073

Fanuc Robot SRVO-073 - CMAL alarm (pulse coder noise or fault)

CMAL alarm (pulse coder noise or fault)

The pulse coder may be faulty or electrical noise is causing it to malfunction. Unlike PMAL, this alarm may be caused by external noise rather than a hardware failure.

Root Cause Summary

SRVO-073 CMAL (Communication Error) indicates the pulse coder communication circuit has detected data transmission errors between the pulse coder and the servo amplifier. Unlike SRVO-075 PMAL which indicates hardware failure, CMAL is primarily triggered by electrical noise interference, grounding issues, or cable degradation affecting signal integrity rather than complete pulse coder failure.

Safety

  • Always verify robot is in a safe stopped state before entering the work envelope
  • Use T1 mode when testing after clearing servo or motion alarms

Causes and Fixes

  1. 1

    Verify cable routing and separation

    Inspect robot interconnection cables from robot base to controller. Ensure pulse coder signal cables maintain minimum 300mm separation from AC power cables, servo motor power lines, and welding equipment. Check that cables are not bundled together with power wiring in the same conduit or cable tray.

    On older installations, check if anyone has added equipment nearby that could generate EMI - VFDs, welding controllers, or induction heaters are common culprits.

  2. 2

    Inspect cable shield grounding at both ends

    At the robot base connection (axis motor connectors), verify the cable shield is properly terminated to the connector backshell and making solid contact with the robot mounting surface. At the controller end, verify shields terminate at the cabinet ground plate via the connector backshells on the servo amplifier panel. Use a DMM to verify continuity between shield and ground (should be <1 ohm).

    Disconnect all power and wait 5 minutes for capacitor discharge before opening controller cabinet or manipulating cables.

  3. 3

    Check for ground loops and grounding configuration

    Verify the robot base is solidly grounded to facility ground. Check that controller cabinet ground is connected to the same ground point (single-point grounding). Measure AC voltage between robot base and controller ground with robot powered on - should be less than 1VAC. Higher voltage indicates ground loop or poor facility grounding.

    If the alarm occurs during specific motions or when certain nearby equipment operates, this strongly points to EMI rather than hardware failure.

  4. 4

    Install or check ferrite cores on pulse coder cables

    If noise issues persist, install snap-on ferrite cores (FANUC part A660-2005-T505 or equivalent) on the pulse coder cables near both ends. Place cores within 100mm of connectors on both robot base side and amplifier side. Ensure at least 2-3 wraps through the core for maximum attenuation.

    On R-30iB controllers with high-speed serial pulse coders, ferrite cores are sometimes pre-installed from factory. Check for their presence before adding more.

Service Recommended confidence

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free