Fanuc SV0433 - Servo alarm: n axis psm undervoltage
The FANUC SV0433 alarm, indicating a low DC link voltage on the servo amplifier, is most commonly caused by incoming AC line voltage sags or failing DC link capacitors in the PSM module. The most likely fix involves verifying and stabilizing the incoming AC power or replacing degraded capacitors in the amplifier unit.
Fanuc SV0433 - Servo alarm: n axis psm undervoltage
SERVO ALARM: n AXIS PSM UNDERVOLTAGE
The DC bus voltage on the servo amplifier converter module has fallen below the minimum threshold (typically <270VDC for 200V class, <540VDC for 400V class systems). This alarm indicates insufficient DC link voltage to safely operate the servo motors and will prevent axis motion. The condition is detected by voltage monitoring circuits in the alpha/beta series servo amplifier PSM (Power Supply Module) or converter unit.
Root Cause Summary
The FANUC SV0433 alarm, indicating a low DC link voltage on the servo amplifier, is most commonly caused by incoming AC line voltage sags or failing DC link capacitors in the PSM module. The most likely fix involves verifying and stabilizing the incoming AC power or replacing degraded capacitors in the amplifier unit.
Safety
Causes and Fixes
Measure AC Input Voltage
Use a true RMS multimeter to measure voltage across L1, L2, and L3 terminals at the servo amplifier while the machine is powered on. Ensure readings are within ±10% of rated voltage (200-230VAC for 200V class, 380-480VAC for 400V class).
Measure during peak load conditions (e.g., during rapid axis movement) to catch intermittent sags.
HIGH VOLTAGE: Ensure proper insulation on probes and wear PPE to avoid electric shock.
Check Voltage Balance
Verify that the voltage difference between phases (L1-L2, L2-L3, L1-L3) is less than 5%. Significant imbalance can cause DC link issues even if individual voltages are within spec.
If imbalance is detected, check upstream power distribution or consult with facility electrician.
Do not proceed with machine operation if imbalance exceeds 5% as it risks further damage.
Monitor Voltage Over Time
Use a data-logging multimeter or power quality analyzer to record AC input voltage for at least 30 minutes during normal operation to detect transient brownouts or sags.
Compare logged data with machine alarm timestamps to correlate voltage drops with SV0433 alarms.
Ensure logging equipment is rated for industrial voltage levels to prevent damage.
Call a technician if:
Prevention
Common Mistakes
Seeing Multiple Alarms?
Seeing another alarm with this one? Enter the code.
AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.
Start freeWas this guide helpful?
Always verify with your machine manual or a certified technician before performing service procedures.