FANUC codes
FANUCServo/AxisIntermediate30-90 minutes

SV0433

Fanuc SV0433 - Servo alarm: n axis psm undervoltage

SERVO ALARM: n AXIS PSM UNDERVOLTAGE

The DC bus voltage on the servo amplifier converter module has fallen below the minimum threshold (typically <270VDC for 200V class, <540VDC for 400V class systems). This alarm indicates insufficient DC link voltage to safely operate the servo motors and will prevent axis motion. The condition is detected by voltage monitoring circuits in the alpha/beta series servo amplifier PSM (Power Supply Module) or converter unit.

Root Cause Summary

The FANUC SV0433 alarm, indicating a low DC link voltage on the servo amplifier, is most commonly caused by incoming AC line voltage sags or failing DC link capacitors in the PSM module. The most likely fix involves verifying and stabilizing the incoming AC power or replacing degraded capacitors in the amplifier unit.

Safety

  • HIGH VOLTAGE: DC link bus capacitors retain lethal voltage (up to 750VDC) for several minutes after power-off. Wait minimum 5 minutes and verify <42VDC with meter before touching internal amplifier components
  • Do not disconnect or test regenerative resistor while machine is powered - high-energy discharge through resistor during deceleration can cause severe burns
  • Lock out main power and verify zero voltage before checking AC input connections - loose connections under load can cause arc flash hazard

Causes and Fixes

  1. 1

    Measure AC Input Voltage

    Use a true RMS multimeter to measure voltage across L1, L2, and L3 terminals at the servo amplifier while the machine is powered on. Ensure readings are within ±10% of rated voltage (200-230VAC for 200V class, 380-480VAC for 400V class).

    Measure during peak load conditions (e.g., during rapid axis movement) to catch intermittent sags.

    HIGH VOLTAGE: Ensure proper insulation on probes and wear PPE to avoid electric shock.

  2. 2

    Check Voltage Balance

    Verify that the voltage difference between phases (L1-L2, L2-L3, L1-L3) is less than 5%. Significant imbalance can cause DC link issues even if individual voltages are within spec.

    If imbalance is detected, check upstream power distribution or consult with facility electrician.

    Do not proceed with machine operation if imbalance exceeds 5% as it risks further damage.

  3. 3

    Monitor Voltage Over Time

    Use a data-logging multimeter or power quality analyzer to record AC input voltage for at least 30 minutes during normal operation to detect transient brownouts or sags.

    Compare logged data with machine alarm timestamps to correlate voltage drops with SV0433 alarms.

    Ensure logging equipment is rated for industrial voltage levels to prevent damage.

DIY Feasiblemedium confidence

Call a technician if:

  • ·If DC link capacitor ripple measurement or PSM module substitution confirms internal amplifier failure and replacement is beyond in-house capability.
  • ·If incoming AC voltage issues persist despite checks and require facility-wide power quality analysis.

Prevention

  • Schedule annual power quality checks to detect and mitigate incoming AC voltage fluctuations.
  • Replace DC link capacitors proactively every 8-10 years as part of preventive maintenance.
  • Ensure proper ventilation and cooling around the servo amplifier to prevent overheating of components like regenerative resistors.

Common Mistakes

  • Attempting DC link measurements on live circuits without proper high-voltage training and CAT III rated equipment.
  • Ignoring incoming power quality issues and focusing only on the amplifier, leading to recurring alarms.
  • Failing to wait adequate time (minimum 10 minutes) for DC link capacitor discharge before accessing internal components, risking electric shock.
  • Not following proper lockout/tagout procedures when accessing electrical components.

Related Alarms

Seeing Multiple Alarms?

Seeing another alarm with this one? Enter the code.

Get machine-aware diagnosis

AxisMD logs alarms against your actual machines, tracks patterns, and gives AI context your manual doesn't have.

Start free

Was this guide helpful?

Always verify with your machine manual or a certified technician before performing service procedures.